S1 series standard inverter
-93-
password can be cancelled by setting P07.00 to 0; if P07.00 is set to a non-zero value, the
parameter will be protected by password. When modifying function parameters through serial
communication, the function of user password also follows above rules.
Function
code
Name
Detailed parameter description
Default
value
Modify
P00 group Basic functions
P00.00
Speed control
mode
1: SVC 1
2: V/F mode
Note:
If 1 is selected, it is required to carry out
motor parameter autotuning first.
2
◎
P00.01
Running
command
channel
0: Keypad
1: Terminal
2: Communication
1
○
P00.02 Reserved
P00.03
Max. output
frequency
Used to set the maximum output frequency of the
inverter. It is the basis of frequency setup and the
acceleration/deceleration.
Setting range: Max. (P00.04, 10.00)
–630.00Hz
50.00Hz
◎
P00.04
Upper limit of
running frequency
The upper limit of running frequency is upper limit
value of inverter output frequency. This value
cannot be more than the maximum output
frequency.
When the set frequency is higher than the upper
limit frequency, the inverter runs at the upper limit
frequency.
Setting range: P00.05
–P00.03 (Max. output
frequency)
50.00Hz
◎
P00.05
Lower limit of
running frequency
The lower limit of running frequency is the lower
limit value of inverter output frequency.
When the set frequency is lower than the lower
limit frequency, the inverter runs at the lower limit
frequency.
Note: Max. output frequency
≥ upper limit
frequency
≥ lower limit frequency.
Setting range: 0.00Hz
–P00.04 (upper limit of
running frequency)
0.00Hz
◎
P00.06
A frequency
command
selection
0: Set via keypad
1: Set via AI1
2: Set via AI2
3: Set via AI3 (up to 2.2kW)
2
○
P00.07
B frequency