S1 series standard inverter
-9-
R
S
T
U
V
W
(+)
(-)
PE
PE
PB
DC reactor
Fig 3.4 400V (18.5kW
–110kW) main circuit diagram
R
S
T
U
V
W
(
+
)
(
-
)
DC reactor
P1
PE
PE
Fig 3.5 400V (132kW and above) main circuit diagram
Note:
1. 132kW and above inverters can be connected to external DC reactors. Before connection, it is
required to take off the copper bar between P1 and (+). 132kW and above inverters can be
connected to external brake unit. DC reactors and brake units are optional parts.
2. 18.5kW
–110kW inverters are equipped with built-in DC reactor.
3. 37kW and below models carry built-in brake units, 45kW
–55kW supports built-in brake unit.
75kW
–400kW supports external brake unit. The models that carry built-in brake unit can also be
connected to external brake resistor. The brake resistor is optional part.
3.3 Product specification
Function description
Specification
Power input
Input voltage (V)
AC 1PH 220V (-15%)
–240V (+10%) rated voltage: 230V
AC 3PH 380V (-15%)
–440V (+10%) rated voltage: 400V
Input current (A)
Refer to
Rated value
Input frequency (Hz)
50Hz or 60Hz, allowable range: 47
–63Hz
Power
output
Output voltage (V)
0
–input voltage
Output current (A)
Refer to Rated value