S1 series standard inverter
-127-
Function
code
Name
Detailed parameter description
Default
value
Modify
BIT12: torque set value (% on)
BIT13: pulse counter value
BIT14: reserved
BIT15: current step of multi-step speed
P07.06
Displayed
parameters 2 of
running state
0x0000
– 0xFFFF
BIT0: analog AI1 value (V on)
BIT1: analog AI2 value (V on)
BIT2: analog AI3 value (V on)
BIT3: high speed pulse HDI frequency
BIT4: motor overload percentage (% on)
BIT5: the inverter overload percentage (% on)
BIT6: ramp frequency given value (Hz on)
BIT7: linear speed
BIT8: AC inlet current (A on)
BIT9
– 15: reserved
0x0000
P07.07
The parameter
selection of the
stop state
0x0000
– 0xFFFF
BIT0: set frequency (Hz on, frequency flickering
slowly)
BIT1: bus voltage (V on)
BIT2: input terminals state
BIT3: output terminals state
BIT4: PID reference (% flickering)
BIT5: PID feedback value (% flickering)
BIT6: torque reference (% flickering)
BIT7: analog AI1 value (V on)
BIT8: analog AI2 value (V on)
BIT9: analog AI3 value (V on)
BIT10: high speed pulse HDI frequency
BIT11: current step of multi-step speed
BIT12: pulse counters
BIT13
– BIT15: reserved
0x00FF
○
P07.08
Frequency
display coefficient
0.01
–10.00
Display frequency=running frequency× P07.08
1.00
○
P07.09
Speed display
coefficient
0.1
–999.9%
Mechanical speed=120×display running
frequency×P07.09/number of motor pole pairs
100.0%
○
P07.10
Linear speed
display coefficient
0.1
–999.9%
Linear speed=mechanical speed×P07.10
1.0%
○
P07.11
Temperature of
rectifier bridge
module
-20.0
–120.0°C
/
●
P07.12
Temperature of
inverter module
-20.0
–120.0°C
/
●
P07.13
Software version
of control board
1.00
–655.35
/
●
P07.14
Accumulated
0
–65535h
/
●