S1 series standard inverter
-124-
Function
code
Name
Detailed parameter description
Default
value
Modify
P06.11
Relay RO1
switch-off delay
Note: P06.08 and P06.09 are valid only when
P06.00=1.
0.000s
○
P06.12
Relay RO2
switch-on delay
0.000s
○
P06.13
Relay RO2
switch-off delay
0.000s
○
P06.14
AO1 output
selection
0: Running frequency
1: Set frequency
2: Ramps reference frequency
3: Running speed
4: Output current (relative to inverter)
5: Output current (relative to motor)
6: Output voltage
7: Output power
8: Set torque value
9: Output torque
10: AI1 input value
11: AI2input value
12: AI3 input value
13: Input value of high-speed pulse HDI/HDIA
14: Set value 1 of Modbus communication
15: Set value 2 of Modbus communication
16 - 21: Reserved
22: Torque current (bipolar, 100% corresponds to
10V)
23: Ramps reference frequency (bipolar)
0
○
P06.15
Reserved
variables
0
○
P06.16
HDO high-speed
pulse output
0
○
P06.17
Lower limit of
AO1 output
-300.0%
–P06.19
0.0%
○
P06.18
Corresponding
AO1 output of
lower limit
0.00V
–10.00V
0.00V
○
P06.19
Upper limit of
AO1 output
P06.17
–300.0%
100.0%
○
P06.20
Corresponding
AO1 output of
upper limit
0.00V
–10.00V
10.00V
○
P06.21
AO1 output filter
time
0.000s
–10.000s
0.000s
○