S1 series standard inverter
-110-
Function
code
Name
Detailed parameter description
Default
value
Modify
Users should select torque boost based on the
load, eg, larger load requires larger torque boost,
however, if the torque boost is too large, the motor
will run at over-excitation, which will cause
increased output current and motor heat-up, thus
degrading the efficiency.
When torque boost is set to 0.0%, the inverter is
automatic torque boost.
Torque boost cut-off threshold: Below this
frequency threshold, the torque boost is valid,
exceeding this threshold invalidates torque boost.
Output voltage
Output
frequency
Cut-off
boost
b
f
f
v
v
Setting range of P04.01: 0.0%: (automatic) 0.1%
–
10.0%
Setting range of P04.02: 0.0%
–50.0%
P04.03
V/F frequency
point 1 of motor 1
When P04.00 =1 (multi-point V/F curve), users
can set V/F curve via P04.03
–P04.08.
V/F curve is usually set according to the
characteristics of motor load.
Note:
V1<V2<V3, f1<f2<f3. If low-frequency
voltage is set too high, motor overheat or
burnt-down may occur, and overcurrent stall or
overcurrent protection may occur to the inverter.
Output voltage
Output
frequency(Hz)
V1
V2
V3
f1
f2
f3
100.0%
b
f
b
V
Setting range of P04.03: 0.00Hz
–P04.05
Setting range of P04.04: 0.0%
–110.0% (rated
voltage of motor 1)
0.00Hz
○
P04.04
V/F voltage point
1 of motor 1
00.0%
○
P04.05
V/F frequency
point 2 of motor 1
0.00Hz
○
P04.06
V/F voltage point
2 of motor 1
0.0%
○
P04.07
V/F frequency
point 3 of motor 1
0.00Hz
○
P04.08
V/F voltage point
3 of motor 1
00.0%
○