S1 series standard inverter
-115-
Function
code
Name
Detailed parameter description
Default
value
Modify
that, the current closed-loop control in the IF
control mode is disabled.
Setting range: 0.00
–20.00 Hz
P05 group Input terminals
P05.00
HDI input type
0x00
–0x11
Ones: HDIA input type
0: HDIA is high-speed pulse input
1: HDIA is digital input
Tens: HDIB input type
0: HDIB is high-speed pulse input
1: HDIB is digital input
Note: up to 2.2kW only there is 1 channel HDI.
0
◎
P05.01
Function of S1
terminal
0: No function
1: Forward running
2: Reverse running
3: 3-wire control/Sin
4: Forward jogging
5: Reverse jogging
6: Coast to stop
7: Fault reset
8: Running pause
9: External fault input
10: Frequency increase (UP)
11: Frequency decrease (DOWN)
12: Clear frequency increase/decrease setting
13: Switch-over between setup A and setup B
14: Switch-over between combination setting and
A setting
15: Switch-over between combination setting and
setup B
16: Multi-step speed terminal 1
17: Multi-step speed terminal 2
18: Multi-step speed terminal 3
19: Multi-step speed terminal 4
20: Multi-step speed pause
21: Acceleration/deceleration time selection 1
22: Acceleration/deceleration time selection 2
23
– 24: Reserved
25: PID control pause
1
◎
P05.02
Function of S2
terminal
4
◎
P05.03
Function of S3
terminal
7
◎
P05.04
Function of S4
terminal
0
◎
P05.05
Function of
HDI/HDIA
terminal
0
◎
P05.06
Function of HDIB
terminal
0
◎