telegram "0", the threshold value is enabled.
When select "yes", the following parameters can be seen.
Parameter "Behaviour when setting the lock"
Options: do not send
the same as logic result =‘0’
the same as logic result=‘1’
This parameter sets the action when the threshold value is disabled.
Select " do not send", no action;
Select "the same as logic result=‘0’", when the object "logic 1/2 block" receives telegram "1", the
object "logic 1/2, 1bit/1byte output" sends the same telegram as with telegram "0".
Select "the same as logic result=‘1’", when the object "logic 1/2 block" receives telegram "1", the
object "logic 1/2, 1bit/1byte output" sends the same telegram as with telegram "1".
Parameter "Behaviour when releasing the lock"
Options: Do not send
Update
This parameter sets the action when the logic is started again.
Select "do not send", when the object "humidity threshold value1/2 block" receives the telegram "0",
if the threshold value changes, “1bit/1byte output, humidity” value will be sent immediately, but not vice
versa.
If selecting "update", when "logic 1/2 bock" receives telegram "0", no matter whether the logic
results change, the value of "logic 1/2, 1bit/1byte output" will be sent immediately.
4.11 parameter window "Timer Page 1" and "Timer Page 2"
Parameter window of Timer Page 1" and "Timer Page 2" is shown in Figure 4.11, here is to set the
relevant parameters of timer. Thermostat panel can set schedule to automatically adjust the work mode.
A thermostat panel has 16 timing times, and each timing time has its own work mode. If the current time
is equal to a timing time, it will automatically switch to the corresponding work mode and send the