Options: do not use
temperature threshold value 1
temperature threshold value 1 inverted
temperature threshold value 2
temperature threshold value 2 inverted
humidity threshold value1
humidity threshold value1 inverted
humidity threshold value 2
humidity threshold value 2 inverted
communication object input A
communication object input A inverted
communication object input B
communication object input B
Here is to set the input value of logic operations, logic input value of logic 1 is input1 ~ input3, logic
input value of logic2 is input4 ~ input5.
If one of the logic input isn't used, the logic input and its logic operations should be ignored.
If in a certain threshold state no telegrams are sent, then in this case logic input is not involved in
the logic operation, equivalent do not use, and if the threshold function is disabled, and in this case
logic input is also equivalent to do not use. If the object value of the threshold value is in an
indeterminate state, logic input doesn't participate in logic operations. If temperature and humidity testing
fail, the relevant logic inputs are not involved in logical operations.
Parameter: The logic function type between input 1 (4) and input 2 (5)"
Options: AND
OR
XOR
This parameter sets the logic operations of "Input 1 (4)" and "Input 2 (5) ". Three kinds of logic
operations relations:"AND", "OR", "XOR"
Parameter "The logic function type between input3 (6) and result of input 1/2 (4/5)"