GVS K-BUS
○
R
KNX/EIB
Thermostat
www.video-star.com.cn
Tel.
:
(
8620
)
39338986
Fax.
:(
8620
)
39338465
30
2h
Parameter of “Period of sending HVAC status” is use for setting the interval of sending HVAV to the
bus recurrently through type of “Output HVAC status”. The HVAC status is updated once every 30
seconds.
Status of type “Output HVAC status”
Bit7
Bit6
Bit5
Bit4
Bit3
Bit2
Bit1
Bit0
Frost
warning
○
1
Dead zone
status
Heating
/Cooling
Temperature
control Disable
/Enable
Frost/Heat
protection
mode
Night
mode
Standby
mode
Comfort
mode
Note
○
1
:
Current temperature ≤ 5
℃,
Value of f
rost warning is “1”.
Parameter “Setpoint adjustment”
Options
:
relative adjustment
absolute adjustment
Parameter of “Setpoint adjustment” is use for setting the adjusting way of the temperature setpoint.
For the option of “relative adjustment”, the temperature setpoint is referred to definite comfortable
temperature setpoint in every mode except the comfort mode.
For the option of “absolute adjustment”, the temperature setpoint of comfort mode, stand by mode,
night mode, protecting mode has its independent temperature setpoint which is not affected by the
temperature setpoint of comfort mode.
The parameter as below is use for setting relative adjusting way on temperature setpoint. It
can be found if you choose the “relative adjustment” from the “Setpoint adjustment”.
——
Parameter “Basic comfort setpoint at heating in 0.1Celsius”
Options
:
0…500
The comfort temperature setpoint can be set here under the heating function. All the temperature