Note: Stop control telegrams is not restricted by the minimum and maximum control value, if the control
values
are negated, stop control telegrams are negated, too.
84
Outdoor temperature
Setpoint
temperature
2byte
C, R, W
9.001 DPT_Value_Temp
This communication object would display when parameter
”
Enable display outdoor temperature
”
Selects “enable”, it is used to
receive outdoor temperature from the bus.
85
Heating standby setpoint
Setpoint
temperature
2byte
C, R, W
9.001 DPT_Value_Temp
This communication object would display when parameter
”
Setpoint adjustment
”
Selects “absolute adjustment”, it is used to
modify the standby mode temperature at heating
86
Heating night setpoint
Setpoint
temperature
2byte
C, R, W
9.001 DPT_Value_Temp
This communication object would display when parameter
”
Setpoint adjustment
”
Selects “absolute adjustment”, it is used to
modify the night mode temperature at heating
87
Setpoint frost protection
Setpoint
temperature
2byte
C, R, W
9.001 DPT_Value_Temp
This communication object would display when parameter
”
Setpoint adjustment
”
Selects “absolute adjustment”, it is used to
modify the frost protection mode temperature at heating
88
Cooling comfort setpoint
Setpoint
temperature
2byte
C, R, W
9.001 DPT_Value_Temp
This communication object is used to modify the comfort mode temperature at cooling
89
Cooling standby setpoint
Setpoint
temperature
2byte
C, R, W
9.001 DPT_Value_Temp
This communication object would display when parameter
”
Setpoint adjustment
”
Selects “absolute adjustment”, it is used to
modify the standby mode temperature at cooling
90
Cooling night setpoint
Setpoint
temperature
2byte
C, R, W
9.001 DPT_Value_Temp
This communication object would display when parameter
”
Setpoint adjustment
”
Selects “absolute adjustment”, it is used to
modify the night mode temperature at cooling
91
Setpoint heat protection
Setpoint
temperature
2byte
C, R, W
9.001 DPT_Value_Temp