Send telegrams
(
fan coil control
):
0…100%
21
fan automatic or fan manual
Fan
1 bit
C, R, T
1.001 DPT_Switch
This communication object is used to switch over fan between auto and manual.
when parameter "Switchover fan between auto and manual" selects "object 'Automatic ON/OFF'",
Send the telegram "1" - fan automatic
Send the telegram "0" - fan manual
when parameter "Switchover fan between auto and manual" selects "object 'Manual ON/OFF'",
Send the telegram "1" - fan manual
Send the telegram "0" - fan automatic
22
Fan manual stage
Fan
1 byte
C, R, T
5.001 DPT_Scaling
This communication object is used to send the control value of fan manual, to change the wind speed.
23
Lock temperature control
Temperature
control
1bit
C, R, W
1.001 DPT_Switch
This communication object is used to disable/enable temperature control, including disable/enable basic
heating/cooling control and additional heating/cooling control. When receiving telegram "1", the object "Basic heating /
cooling control value" and object "additional heating / cooling control value" stop sending control telegrams; when
receiving telegram "0", they update control value immediately.
Receive telegram "1" - disable temperature control
Receive telegram "0" - enable temperature control
Note: Stop control telegrams is not restricted by the minimum and maximum control value, if the control
values
are negated, stop control telegrams are negated, too.
26
Lock additional stage
Temperature
control
1bit
C, R, W
1.001 DPT_Switch
This communication object is used to disable or enable additional heating/cooling control. When receiving telegram
"1", the object "additional heating / cooling control value" stop sending control telegrams; when receiving telegram "0", it
updates control value immediately.
Receive telegram "1" - disable additional heating / cooling control value
Receive telegram "0" - enable additional heating / cooling control value