GVS K-BUS
○
R
KNX/EIB
Thermostat
www.video-star.com.cn
Tel.
:
(
8620
)
39338986
Fax.
:(
8620
)
39338465
75
C,T
This communication object is used to receive telegram value from the bus to switch the backlight brightness of backlit
screen.
Received telegram values:
1——the backlight brightness of backlit screen in daytime
0——the backlight brightness of backlit screen at night.
5.2 "Heating/cooling control “Communication Object
Figure 5.2 Temperature control communication object
No
Object name
Functions
Data Types
Flags
DPT
2
Input external temperature
Temperature
2 byte
C, R,W
9.001 DPT_Value_Temp
This communication object is for receiving temperature the external temperature sensor sends on the bus.
3
Actual temperature
Temperature
2 byte
C, R, T
9.001 DPT_Value_Temp
The communication object is used to send the current temperature that is detected by the thermostat panel sensor, to
the bus; the transmission time is set via parameter settings.
When there is an external temperature sensor, the object is used to send the proportion and sum of temperatures sent