GVS K-BUS
○
R
KNX/EIB
Thermostat
www.video-star.com.cn
Tel.
:
(
8620
)
39338986
Fax.
:(
8620
)
39338465
77
The communication object is visible when the object type of operating mode is "1bit", and is used to activate standby
mode. Receiving telegram "1"will activate standby mode; receiving telegram "0" will not activate standby mode.
Receive telegram "1"----activate standby mode
Receive telegram "0"----not activate standby mode
10
Active night mode
Setpoint
temperature
1 bit
C,R,W
1.001 DPT_Switch
The communication object is visible when the object type of operating mode is "1bit", and is used to activate night
mode. Receiving telegram "1"will activate night mode; receiving telegram "0" will not activate night mode.
Receive telegram "1"----activate night mode
Receive telegram "0"----not activate night mode
11
Active frost/heat protection
mode
Setpoint
temperature
1 bit
C, R,W
1.001 DPT_Switch
The communication object is visible when the object type of operating mode is "1bit", and is used to activate the frost
/heat protection mode. Receiving telegram "1"will activate the frost /heat protection mode; receiving telegram "0" will not
activate the frost /heat protection mode.
Receive telegram "1"----activate the frost /heat protection mode
Receive telegram "0"----not activate the frost /heat protection mode
12
Temperature operating mode
switchover
Setpoint
temperature
1 byte
C, R,W
20.102 DPT_HVACMode
The communication object is visible when the object type of operating mode is "1bit", and is used to switch to RTC
mode. Different telegrams mean different operating modes, as follows: 0: Auto (comfortable), 1: comfort mode, 2: Standby
mode, 3: Night Mode, 4: Frozen protection /heat protection, 5~255: Reserved, do not use. For example, when an object
receives a telegram "2", the thermostat panel will control the actuator according to the standby mode setting.
Communication object of operating mode switching has priority; thermostat panel activates the operating mode
according to the priority of a communication object of operating mode. More information is seen in 4.4 "Object type for
operating mode switchover".
13
Heating/cooling switchover
Temperature
control
1bit
C, R, W
1.100 DPT_Heat/Cool