When select "yes", the following parameters can be seen.
Parameter "Behaviour when setting the lock"
Options: Do not send telegram
Send the same telegram as lower threshold
Send the same telegram as upper threshold
This parameter sets the action when the threshold value is banned.
Select “do not send", no action;
Select "Send the same telegram as lower threshold", when the object "humidity threshold value1/2
block" receives telegram "1", the object "1bit/1byte output, humidity" sends the same telegram as lower
threshold.
Select "Send the same telegram as upper threshold", when the object "humidity threshold value1/2
block" receives telegram "1", the object "1bit/1byte output, humidity" sends the same telegram as higher
threshold.
This parameter can be seen in "use block of the humidity threshold output" if User selects "yes".
Parameter "Behaviour when releasing the lock"
Options: Do not send
Update
This parameter sets the action when the threshold value is started again.
Select "do not send", when the object "humidity threshold value1/2 block" receives the telegram "0",
if the threshold value changes, “1bit/1byte output, humidity” value will be sent immediately, but not vice
versa. If the current humidity is between high and low thresholds, no telegram will be sent; if loop
sending is enabled, the previous telegram will be loop sent.
Select "update", when the object "humidity threshold value1/2 block" receives telegram "0", the
object "1bit/1byte output, temperature" updates according to the threshold range of the current humidity,
no matter whether the object value changes, the telegram is sent. If the current humidity is between the
high and low thresholds, the object value cannot be determined, the telegram is not sent, even though in
case of sending cyclically.
This parameter can be seen in "use block of the humidity threshold output" if User selects "yes".