This communication object would display when parameter
”
Setpoint adjustment
”
Selects “absolute adjustment”, it is used to
modify the heat protection mode temperature at cooling
5.3 "Threshold value" communication object
Figure 5.3 Threshold value communication object
Number
Object name
Functions
Data Types
Flags
DPT
27/31
Chang temperature threshold
value 1/2
Temperature threshold value 1/2
2byte
C, R, W
9.001
DPT_Value_Temp
This communication object is used to change the temperature's high threshold value.
Telegram:
0…50
℃
28/32
1 bit output temperature
Temperature threshold value 1/2
1bit
C, R,T
1.001 DPT_Switch
When the temperature is higher than the current high threshold or below the low threshold, 1bit telegram can be sent via this
object to the bus, specific telegrams can be set by the parameter "logic 1bit telegram value [0 ... 1]".
29/33
1 byte output temperature
Temperature threshold value 1/2
1byte
C, R,T
5.010
DPT_Value_1_Ucount
When the temperature is higher than the current high threshold or below the low threshold, 1bit telegram can be sent via this
object to the bus, specific telegrams can be set by the parameter "1byte telegram value[0…255]".
30/34
Temperature threshold value
1/2 block
Temperature threshold value 1/2
1bit
C, R,W
1.001 DPT_Switch
This communication object is used to disable or enable the function of the temperature threshold value. Disabled and enabled
actions can be set by the parameter.
Receive telegram "1" - disable the temperature threshold value
Receive telegram "0" - enable the temperature threshold value