The parameter will be visible when the parameter "Indoor and outdoor temperature" selecting
"enable" ,which is used to set the time interval for the internal temperature and external temperature
alternately.
Parameters "Humidity correction in%"
Optional: -15 ..15
This parameter defines the correction settings of humidity that sensor measured to prevent much
error between the moisture measurement with the actual humidity.
For example, setting correction
value to 1%, if the humidity measured by the sensor is 40%, then the corrected humidity is 40% + 1% =
41%.
Parameters "Send rel. Humidity at variation of (%)"
Options: Do not send
1
2
...
20
This parameter defines to change when humidity change a certain amount, the communication
object "rel. Humidity" can send current humidity to the bus.
If choosing "do not send", humidity measurements are not automatically sent to the bus, can sent
automatically after be read through communication objects "rel. Humidity".
If choosing "3", the communication object "rel humidity" will send to the current temperature on the
bus when the humidity changed to 3%.
Parameters "Period of sending humidity"
Options: Do not send
5s
10s
..
2h