Description
The SZ1017a, SZ1041, SZ1051 and SZ1053 are microproces-
sor-based programmable thermostats designed to control air
handling units with modulating economizers and/or modulat-
ing heating or cooling. The SZ1041, SZ1051 and SZ1053
have a 365-day time clock, while the SZ1017a has a 7-day
time clock.
Features
!
Stand-alone or network operation
!
Outdoor air sensor input with heating & cooling lockout
!
Adjustable delay on powerup for soft starts
!
P+I control option
!
Smart Recovery
!
No battery backup required
!
Built-in HVAC equipment protection
!
32 character LCD display
!
Six status LEDs for monitoring
!
Remote room sensing capability
!
User setpoint adjustment limits
!
Local and remote override capability
!
System and fan switching with access lockouts
!
Equipment monitoring inputs and indication
!
External time clock input
!
Access to programming or schedule may be locked out or
limited with the use of an access code
!
Fahrenheit or Celsius temperature display
Contents
Description
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1
Features
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1
Mounting
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1
Wiring
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2
Setup
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4
Programming
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5
Setting Clock & Schedule
. . . . . . . . . . . . . . . . . . . . . . . . .
11
Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
Checkout & Troubleshooting
. . . . . . . . . . . . . . . . . . . . . . .
14
LED Description
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
15
Limiting Occupant Access . . . . . . . . . . . . . . . . . . . . . . . . .16
User’s Guide
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
16
Mounting
The SZ1017a, SZ1041, SZ1051 and SZ1053 are designed for
wall mounting using two #6 sheet metal screws, either over a
horizontally installed 2" x 4" junction box, or directly to block
or drywall.
For best results, the thermostat should be mounted on an inte-
rior wall which reflects normal room environment, at a height
of approximately five feet from the floor. Avoid areas exposed
to direct sunlight, unusual heat sources, open doors and win-
dows, or unventilated locations.
If using a remote room sensor, it should be mounted in the
manner described above. The thermostat may then be mounted
in an area which is accessible for adjusting its settings.
Caution
: Remove power from thermostat prior to
mounting.