Setup
Note:
If using remote sensor(s), the calibration may need to
be adjusted. See “Checkout and Troubleshooting” section.
TEMPERATURE SENSOR SELECTION
The dipswitches in the cover (shown above) must be set when
using remote room, discharge, and/or outdoor sensors.
Use the following guide to determine the dipswitch settings
for your application.
Using built-in room sensor only.
(This is the default setting.)
Using built-in room sensor with
discharge air sensor only.
Using built-in room sensor with
outdoor air sensor only.
Using built-in room sensor with
both discharge and outdoor air
sensors.
Using remote room sensor only.
Using remote room sensor with
discharge air sensor only.
Using remote room sensor with
outdoor air sensor only.
Using remote room sensor with both
discharge and outdoor air sensors.
KEYPAD ACCESS
The dipswitches in the cover (shown above connected with
ribbon cable) must be set in order to lock the user out of pro-
gramming and/or to set the clock and schedule. Use the guide
below to set these dipswitches for your application. User
access may also be limited with an access code set in pro-
gramming. (The fan and system switches are enabled or dis-
abled in programming only, and require no dipswitch place-
ment.)
Keypad access to both programming
and clock setup. (This is the default
setting.)
No keypad access to programming or
clock setup.
Keypad access to programming only.
Keypad access to clock setup only.
Once the dipswitches have been set and you have confirmed
that the sensors are reading correctly (and program and clock
setup are finished, if locking out access with dipswitches),
secure the cover to the base with the two set screws located at
the top right and the left side to prevent tampering.
1 2 3 4 5
1 2 3 4 5