background image

2800 LAURA LANE 

MIDDLETON, WI 53562 

(800) 288-9383 

FAX (608) 836-9044 

www.tcs-basys.com

2

Wiring                               

The SZ1017a, SZ1041, SZ1051 and SZ1053 use standard ter-

minal designations for wiring. See diagram below.

REMOTE TEMPERATURE SENSOR WIRING

Use 18 AWG shielded twisted-pair grounded at the sensor

mounting location. Sensor wiring runs of up to 250 feet are

attainable if properly shielded wire is used and the installation

environment is free of electrical noise. Sensor wire should be

kept at least five feet away from line voltage wiring.

The SZ1017a, SZ1041, SZ1051 and SZ1053 accept three 2-

wire remote temperature sensors. Consult the TS Series

Temperature Sensor Submittal Data sheet for a complete list-

ing of packaging and application styles. When using

TCS/Basys Controls three-wire sensors, use the black and red

leads and either clip or twist off the white lead. Make sure that

the dip switches are set for the sensors you are using.

POWERING THE SZ1017a, SZ1041, SZ1051 and SZ1053

Superstats are powered from 24 VAC +/- 20%. 

If wiring for communications, dedicated power must be used

to power the Superstat. Several “S” Series thermostats may be

powered from the same transformer, provided that the trans-

former has sufficient power.   (Superstats require 8 VA @ 24

VAC.)

Caution: 

Do not connect to 120 VAC.  When mul-

tiple TCS/Basys Controls devices are using a single

transformer, the polarity of the power wiring must

be maintained because all TCS devices are half-

wave rectified and have common return paths.

When the Superstat is used as a stand-alone thermostat with-

out communications, the unit transformer may be used to

power it. To do this, install a jumper between the “R” and

“+24” terminals.  The “24-” terminal must then be connected

to the common side of the unit transformer.

1

For communication wiring, use twisted, shielded 18 AWG.
Must be run separately.

2

Dry momentary contact. Must not be powered.

3

24 VAC transformer. See powering instructions.

4

5

Sensor input wiring 18 AWG, twisted, shielded pair.

Dry contact. Must not be powered.

6

4 to 20 mA output. 600 ohm max. Do not power actuator with
power from the thermostat. The thermostats are half-wave
rectified, whereby the power ground is common with the signal
ground.

3

4

4

4

5

5

5

Remote

Zone/Return

Air Temp

Discharge

Air Temp

Outside

Air Temp

2

Input Wiring for the SZ1017a, SZ1041,
SZ1051 and SZ1053

For communication wiring, use twisted, shielded 18 AWG.
Must be run separately.

Dry momentary contct. Must not be powered.

24 VAC transformer. See powering instructions.

Dry contact. Must not be powered.

Sensor input wiring 18 AWG, twisted, shielded pair.

4 to 20 mA output 600 ohm max. Do not power actuator with power
from the thermostat. The thermostats are half-wave rectified, whereby
the power ground is common with the signal ground.

Up to nominal 28 VAC from equipment transformer.

Summary of Contents for SZ1017a

Page 1: ...nt monitoring inputs and indication External time clock input Access to programming or schedule may be locked out or limited with the use of an access code Fahrenheit or Celsius temperature display Contents Description 1 Features 1 Mounting 1 Wiring 2 Setup 4 Programming 5 Setting Clock Schedule 11 Operation 11 Checkout Troubleshooting 14 LED Description 15 Limiting Occupant Access 16 User s Guide...

Page 2: ...S Basys Controls devices are using a single transformer the polarity of the power wiring must be maintained because all TCS devices are half wave rectified and have common return paths When the Superstat is used as a stand alone thermostat with out communications the unit transformer may be used to power it To do this install a jumper between the R and 24 terminals The 24 terminal must then be con...

Page 3: ... B R 1 G Y1 or W1 Y2 or W2 6 Time Clock Output 7 Output Wiring for the SZ1017a A B 1 6 7 Output Wiring for the SZ1041 A B R 1 G Y1 or W1 Y2 or W2 Time Clock Output 6 6 7 Output Wiring for the SZ1051 A B R 1 G Y1 or W1 Y2 or W2 Time Clock Output CWV 6 HWV 6 7 Output Wiring for the SZ1053 ...

Page 4: ...nly Using remote room sensor with both discharge and outdoor air sensors KEYPAD ACCESS The dipswitches in the cover shown above connected with ribbon cable must be set in order to lock the user out of pro gramming and or to set the clock and schedule Use the guide below to set these dipswitches for your application User access may also be limited with an access code set in pro gramming The fan and...

Page 5: ...ing 248 Communication Baud Rate Screen If using a PC to access the thermostat all controllers on a network must be set to the same baud rate Choose between 2 4K 4 8K 9 6K and 19 2K program setup program setup program setup program setup program setup program setup program setup 11 UNOCCUPIED HEAT SETPOINT OCCUPIED HEAT 10 SETPOINT SET UNOCCUPIED FAN MODE 9 8 SET OCCUPIED FAN MODE USER ACCESS TO FA...

Page 6: ... the auxiliary output will be OPEN during occupied periods and closed during unoccupied periods or CLOSED during occupied periods and open during unoccupied periods program setup program setup program setup program setup 48 DI3 USED FOR FILTER SERVICE 47 ENABLE SMART YES RECOVERY SET DI2 SETPOINT 02F SHIFT 46 DELAY ON POWERUP 60 SECONDS DI2 USED FOR MONITOR DI3 USED FOR FILTER SERVICE 45 DI1 USED ...

Page 7: ...P 70F COOLING LOCKOUT 28b TEMP 65F ENABLE OUTDOOR AIR SENSOR 27b YES program setup program setup program setup program setup program setup program setup program setup program setup ECON CONTROL 37b ACTION DIRECT 36b ECON OUTPUT RANGE 4 20mA OUTDOOR DAMPER MIN POSITION 35b 10 DSCHRGE AIR ECON 34b PROP BAND DSCHRGE AIR ECON 33b DSCHRGE AIR ECON 32b SETPOINT 55F 31b OUTDOOR AIR ECON SETPOINT 65F 30b ...

Page 8: ...nsor function is disabled Discharge Air Economizer Screen Set the discharge air setpoint This screen will not appear if the discharge air sensor function is disabled program setup DSCHRGE AIR ECON 33a 32a program setup COOL STAGE 1 OFFSET 0F DSCHRGE AIR ECON program setup program setup COOLING LOCKOUT 38a 37a 36a ENABLE OUTDOOR AIR SENSOR 35a ECON CONTROL 34a ACTION program setup program setup DI3...

Page 9: ...t also be set program setup program setup program setup MO 1 DISCHARGE 38c 37c 36c MOD OUT 2 BASED ON 35c MOD OUT 1 BASED 34c ON program setup program setup DI3 USED FOR FILTER SERVICE 39c MO 2 DISCHARGE SETPOINT program setup program setup program setup 43c COOLING LOCKOUT TEMP 60F 42c ENABLE SMART YES RECOVERY ENABLE OUTDOOR YES AIR SENSOR 41c DELAY ON POWERUP 60 SECONDS MO 2 RESET RATIO DI3 USE...

Page 10: ...ir Low Limit Screen Enter a discharge air low limit value This screen will not appear if the discharge air sensor function is disabled DISCHARGE AIR 31d HIGH LIMIT 120F program setup program setup program setup program setup program setup program setup program setup HEATING LOCKOUT 37d TEMP 70F COOLING LOCKOUT 36d TEMP 65F ENABLE OUTDOOR 35d AIR SENSOR YES RESET RATIO 34d 2F FACTOR 33d DISCHARGE A...

Page 11: ...ay still be activated SET OCCUPIED A 08 00 TO 12 00 4 5 TIMES MONDAY B 13 00 TO 17 00 SET OCCUPIED 6 TIMES TUESDAY The following screens are repeated for Wed Thurs Fri Sat and Sun Holiday 1 and 2 COPY MON FOR TUE 7 8 A 08 00 TO 12 00 B 13 00 TO 17 00 clock setup override clock setup clock setup clock setup override MON 72F 12 00 AM SET DATE 11 19 01 3 1 clock setup ENTER ACCESS SET TIME DAY MON 12...

Page 12: ... econ omizer On the SZ1051 analog output one is used to control the heating or cooling in a space while analog output two is used to control an economizer ANALOG OUTPUTS DISCHARGE AIR RESET SZ1017a SZ1053 The analog output on the SZ1017a is used to control the heat ing or cooling in a space The analog outputs on the SZ1053 are used to control the heating and cooling in a space To use the discharge...

Page 13: ... cooling ANALOG OUTPUT PARAMETERS Use programming steps 23d through 28d for the SZ1017a or 23a through 28a for the SZ1051 or 23c through 32c SZ1053 to program the operating parameters for the analog output Select whether the analog output is set for heating cooling or aquastat SZ1017a and SZ1051 Select direct or reverse action Select whether you want the analog output to modulate from 4 to 20mA or...

Page 14: ... rated at 24 VAC For loads that exceed this use an external relay It may be set to be open NO or closed NC when the thermostat is operating in the occupied mode and will be the opposite during the unoccupied mode BUILT IN DELAYS The SZ1017a SZ1041 SZ1051 and SZ1053 have delays built into the programming sequences to protect equipment The fan has a minimum on and off time of 30 seconds When the fan...

Page 15: ...sequence off The fan will turn off 2 minutes after the last heating stage 8 Press the cooler button until the cooling setpoint is less than the current temperature by at least five degrees The fan will come on The cooling stage s will sequence on after 2 min utes 9 Press the warmer button until the cooling setpoint is greater than the current temperature by one degree The cooling stage s will sequ...

Page 16: ...tput Not Working Properly Check wiring A separate transformer should be used for the SZ1017a SZ1041 SZ1051 or SZ1053 and a separate trans former should be used for the motor s Check to make sure that the analog output is programmed correctly Check the Service Menu The Mod Out Screen will tell you what the SZ1041 or SZ1051 is trying to put out Compare this with the actual position on the heating or...

Page 17: ...l monitoring is available by continually pressing the service key FOR THE SZ1053 FOR THE SZ1017a Occupied Heating Cooling Fan Service Program Data Limiting Occupant Access SETPOINT ADJUSTMENT The occupant may temporarily change the occupied heating and cooling setpoints 5 F by factory default This setpoint change will remain until the end of the current occupied peri od at which time the program r...

Page 18: ...e is designed to assist the installer in explaining to the end user how to operate their new thermo stat as well as serve as a handy future reference for the end user We recommend that the installer fill out the appropriate pages and explain to the user how the thermostat operates what settings may be changed and how the time clock sched ules are used S U P E R S T A T TM Rev 0900 ...

Reviews: