ADV100 • Functions description and parameters list
73
perform rapid current variations when load steps are suddenly applied.
A value of 5% allows a very fast response to load steps but with a loss of output voltage and thus power output (re-
duced power output).
The minimum value (1%) allows a maximum output voltage (around 98%) of the mains voltage to be achieved but
with loss of quality of the dynamic response.
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
Mod
19.13 2300 Minimum speed OL
rpm INT16
30
0
CALCI
ERW __S
Setting of the minimum speed threshold in the sensorless vector control mode. Below this limit the sensorless regu-
lator is disabled.
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
Mod
19.14 2302 Min speed delay OL
ms
UINT16
200
0
5000
ERW __S
Setting of the delay for disabling the sensorless regulator.
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
Mod
19.15 2304 Speed filter OL
ms
FLOAT
5.0
0.1
20.0
ERWZ __S
Setting of the time constant for the estimated speed in sensorless vector mode. By increasing this parameter it is
possible to reduce the level of disturbance of the estimated speed, but the speed control dynamics are also lowered.
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
Mod
19.16 2306 Flux observe gain OL
FLOAT
250.0
10.0
5000.0
ERW __S
Flux observer gain in open-loop flux vector control mode.
In case of instability, try changing the value and setting half or twice the default value.
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
Mod
19.17 2310 Flux weakening OL
ENUM
Enable
0
1
ERWZ __S
Enables or disables flux reduction in the open-loop flux vector control mode.
If set to Disable, the flux is not reduced when the speed of the motor exceeds the nominal speed. This results in loss
of control and instability.
To prevent this problem, set the parameter to Enable.
In the open-loop mode a flux value of less than the nominal speed of the motor is advantageous in terms of stability.
0
Disable
1
Enable
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
Mod
19.18 2320 Magnetization time
ms
UINT16
256
128
4096
ERWZ __S
This parameter is used to slow down the magnetisation transient and prevent the motor shaft from rotating due to
the alignment of the stator and rotor.
Summary of Contents for SIEIDrive ADV100
Page 1: ... Functions description and parameters list SIEIDrive Field oriented vector AC Drive ADV100 ...
Page 28: ...28 ADV100 Functions description and parameters list Ramp freeze Ramp Output Motor speed ...
Page 152: ...152 ADV100 Block Diagrams F Block Diagrams System Diagrams Index Drive overview ...
Page 153: ...ADV100 Block Diagrams 153 References ...
Page 154: ...154 ADV100 Block Diagrams Ramps Braking ...
Page 155: ...ADV100 Block Diagrams 155 Multireference ...
Page 156: ...156 ADV100 Block Diagrams Motorpotentiometer Jog function ...
Page 157: ...ADV100 Block Diagrams 157 Monitor function ...
Page 158: ...158 ADV100 Block Diagrams ...
Page 159: ...ADV100 Block Diagrams 159 Commands ...
Page 160: ...160 ADV100 Block Diagrams ...
Page 161: ...ADV100 Block Diagrams 161 Digital inputs Digital outputs ...
Page 162: ...162 ADV100 Block Diagrams Analog inputs ...
Page 163: ...ADV100 Block Diagrams 163 Analog outputs Encoder config ...
Page 164: ...164 ADV100 Block Diagrams Speed reg gains ...
Page 165: ...ADV100 Block Diagrams 165 Torque config ...
Page 166: ...166 ADV100 Block Diagrams VF parameters ...
Page 167: ...ADV100 Block Diagrams 167 Functions ...
Page 168: ...168 ADV100 Block Diagrams ...
Page 169: ...ADV100 Block Diagrams 169 ...
Page 170: ...170 ADV100 Block Diagrams PID application ...
Page 171: ......