ADV100 • Functions description and parameters list
103
23 – COMMUNICATION
23.1 - COMMUNICATION/RS232
The ADV100 drive is provided with a standard port (9 pole sub-D connector: XS) for connecting the RS232 serial line
used for drive-PC point-to-point communication (via the GF-eXpress configuration software).
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
Mod
23.1.1 3800 Drive address
UINT16
1
1
255
ERW FVS
Setting of the address to which the drive responds when connected to the RS232 serial line.
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
Mod
23.1.2 3802 Serial baudrate
ENUM
38400
0
2
ERW FVS
Setting of the RS232 serial communication speed (Baud Rate).
0
9600
1
19200
2
38400
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
Mod
23.1.3 3810 Serial parameter
ENUM
None,8,1
0
3
ERW FVS
Setting of the format of the RS232 serial line.
0
None,8,1
1
None,8,2
2
Even,8,1
3
Odd,8,1
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
Mod
23.1.4 3804 Serial protocol
ENUM
Modbus
0
1
ERW FVS
Setting of the serial communication protocol:
0
Modbus
1
Jbus
Setting to
0
selects the Modbus RTU (Remote Terminal Unit) serial communication protocol.
Setting to
1
selects the Jbus serial communication protocol. The Jbus protocol is functionally identical to the Modbus,
except for the different numbering of addresses: in the Modbus these start from zero (0000 = 1st address) while in
the JBUS they start from one (0001 = 1st address) and maintain this difference throughout numbering.
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
Mod
23.1.5 3806 Serial delay
ms
UINT16
0
0
1000
ERW FVS
Setting of the minimum delay between the drive receiving the last byte and starting its response. This delay avoids
conflicts on the serial line when the RS232 interface that is used has not been pre-set for automatic Tx/Rx switching.
The parameter only concerns the use of the standard RS232 serial line.
Example: if the delay in Tx/Rx switching on the master is a maximum of 20ms, the
Ser answer delay
parameter
must be set to at least 20ms: 22ms
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
Mod
23.1.6 3808 Serial swap data
BIT
0
0
1
ERW FVS
This parameter enables the exchange of the reading of the High and Low parts of the words for FLOAT type param-
eters when using the Modbus protocol.
Summary of Contents for SIEIDrive ADV100
Page 1: ... Functions description and parameters list SIEIDrive Field oriented vector AC Drive ADV100 ...
Page 28: ...28 ADV100 Functions description and parameters list Ramp freeze Ramp Output Motor speed ...
Page 152: ...152 ADV100 Block Diagrams F Block Diagrams System Diagrams Index Drive overview ...
Page 153: ...ADV100 Block Diagrams 153 References ...
Page 154: ...154 ADV100 Block Diagrams Ramps Braking ...
Page 155: ...ADV100 Block Diagrams 155 Multireference ...
Page 156: ...156 ADV100 Block Diagrams Motorpotentiometer Jog function ...
Page 157: ...ADV100 Block Diagrams 157 Monitor function ...
Page 158: ...158 ADV100 Block Diagrams ...
Page 159: ...ADV100 Block Diagrams 159 Commands ...
Page 160: ...160 ADV100 Block Diagrams ...
Page 161: ...ADV100 Block Diagrams 161 Digital inputs Digital outputs ...
Page 162: ...162 ADV100 Block Diagrams Analog inputs ...
Page 163: ...ADV100 Block Diagrams 163 Analog outputs Encoder config ...
Page 164: ...164 ADV100 Block Diagrams Speed reg gains ...
Page 165: ...ADV100 Block Diagrams 165 Torque config ...
Page 166: ...166 ADV100 Block Diagrams VF parameters ...
Page 167: ...ADV100 Block Diagrams 167 Functions ...
Page 168: ...168 ADV100 Block Diagrams ...
Page 169: ...ADV100 Block Diagrams 169 ...
Page 170: ...170 ADV100 Block Diagrams PID application ...
Page 171: ......