ADV100 • Functions description and parameters list
131
11074
(2)
(1)
(3)
(1) Set point
(2) Feedback value
Example:
suppose parameter 11002
Set point val
of a pump pressure control is 10 bar, 11070
Const pressure thr
is set to 5%, 11074
Const press offset
is set to 4% and 11076
Fluid loss thr
= 1% with 11078
Fluid loss thr time
= 0.6 seconds
This means that to move to the constant pressure condition the feedback must be more than 9.5 bar.
We can consider 2 cases for restarting:
Case 1: the liquid leakage causes the pressure to fall by 0.1 bar per second
In this case the change is lower than the set threshold and to restart the drive the feedback must be less than 9.1
bar due to the settings in parameter 11074
Const press offset
.
Case 2: the liquid leakage causes the pressure to fall by 0.2 bar per second
In this case the change exceeds that set in PAR 11076
Fluid loss thr
(0.1 bar every 0.6 secongs). After 0.6 seconds
(from when the constant pressure threshold is exceeded) the pressure feedback is 9.38 bar, a leakage is detected
and the drive is restarted.
ALARMS
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
Mod
11050 Feedback loss time
sec
FLOAT
0.00
0
10000
RW FVS
This parameter defines the time for recognising the loss of the feedback signal.
The alarm is only recognised if parameter 11004
Feedback sel
is set to PAR 1600
Analog input 1X mon
and PAR
1650
Analog input 2X mon
.
The drive recognises the alarm if the feedback signal is equal to zero (no signal) for longer than the time set in PAR
11050
Feedback loss time
. If this parameter is set to zero, the alarm is not recognised.
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
Mod
11052 Feedback loss act
ENUM
Stop
0
4
RW FVS
This parameter defines drive activity following the recognition of a
Perdita retroaz PID
alarm.
0
Ignore
1
Warning
2
Disable
3
Stop
4
Faststop
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
Mod
11054 Feedback level
%
FLOAT
20.000
1.000
50.000
RW FVS
This parameter defines the error level (expressed as a percentage with respect to the set point) for generating the
PID FB loss
alarm.
The alarm is generated when the PID error is higher than the set threshold.
Summary of Contents for SIEIDrive ADV100
Page 1: ... Functions description and parameters list SIEIDrive Field oriented vector AC Drive ADV100 ...
Page 28: ...28 ADV100 Functions description and parameters list Ramp freeze Ramp Output Motor speed ...
Page 152: ...152 ADV100 Block Diagrams F Block Diagrams System Diagrams Index Drive overview ...
Page 153: ...ADV100 Block Diagrams 153 References ...
Page 154: ...154 ADV100 Block Diagrams Ramps Braking ...
Page 155: ...ADV100 Block Diagrams 155 Multireference ...
Page 156: ...156 ADV100 Block Diagrams Motorpotentiometer Jog function ...
Page 157: ...ADV100 Block Diagrams 157 Monitor function ...
Page 158: ...158 ADV100 Block Diagrams ...
Page 159: ...ADV100 Block Diagrams 159 Commands ...
Page 160: ...160 ADV100 Block Diagrams ...
Page 161: ...ADV100 Block Diagrams 161 Digital inputs Digital outputs ...
Page 162: ...162 ADV100 Block Diagrams Analog inputs ...
Page 163: ...ADV100 Block Diagrams 163 Analog outputs Encoder config ...
Page 164: ...164 ADV100 Block Diagrams Speed reg gains ...
Page 165: ...ADV100 Block Diagrams 165 Torque config ...
Page 166: ...166 ADV100 Block Diagrams VF parameters ...
Page 167: ...ADV100 Block Diagrams 167 Functions ...
Page 168: ...168 ADV100 Block Diagrams ...
Page 169: ...ADV100 Block Diagrams 169 ...
Page 170: ...170 ADV100 Block Diagrams PID application ...
Page 171: ......