
134
ADV100 • Functions description and parameters list
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
Mod
956
Speed thr 1_2 mon
BIT
16
0
0
1
ER
To display the speed threshold status: if the motor speed is higher than the value set in parameter
950
Speed
threshold 1
or lower than the value set in parameter
952 Speed threshold 2
this parameter assumes the value of
0.
If the motor speed is between the value of
950
Speed threshold 1
and that of
952 Speed threshold 2
, this param-
eter assumes the value of 1.
Use parameter
954 Speed threshold dly
to set a delay time for the transition from 0 to 1 of parameter
956 Speed
thr 1_2 mon
; the transition from 1 to 0 is always immediate.
When
950
Speed threshold 1
is set to a value higher than
952 Speed threshold 2
, if the motor speed is between
the thresholds this parameter assumes the value of 1. If
950
Speed threshold 1
is set to a value lower than
952
Speed threshold 2
, the threshold status is not significant
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
Mod
966
Set speed
BIT
16
0
0
1
ER
This signal is active when the error between the speed reference and actual motor speed is greater than the toler-
ance set in parameter
962 Set speed error
.
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
Mod
976
Speed thr 3 mon
BIT
16
0
0
1
ER
The status of the block that detects exceeding of the speed 3 threshold is displayed.
0
Actual speed below threshold
1
Actual speed above threshold
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
Mod
986
Current thr mon
BIT
16
0
0
1
ER
The status of the block that detects exceeding of the current threshold is displayed.
0
Actual output current below threshold
1
Actual output current above threshold.
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
Mod
1030 Local/remote mon
BIT
16
0
0
1
ER
This signal is active when the drive is in the
Remote
operating mode.
0
Local
1
Remote
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
Mod
1060 Sequencer status
UINT16 16
0
0
0
ER
This signal indicates the state of the “machine states” that controls drive operation.
STS_INIT
0
STS_MAGN
1
STS_STOP
2
STS_START
3
STS_FS_STOP
4
STS_FS_START
5
STS_QSTOP
6
STS_FS_MAGN
7
STS_W_QSTOP
8
STS_READY
9
STS_MAGN_START
10
STS_ALM_DISABLED
11
STS_ALM_END_ACTION
12
Summary of Contents for SIEIDrive ADV100
Page 1: ... Functions description and parameters list SIEIDrive Field oriented vector AC Drive ADV100 ...
Page 28: ...28 ADV100 Functions description and parameters list Ramp freeze Ramp Output Motor speed ...
Page 152: ...152 ADV100 Block Diagrams F Block Diagrams System Diagrams Index Drive overview ...
Page 153: ...ADV100 Block Diagrams 153 References ...
Page 154: ...154 ADV100 Block Diagrams Ramps Braking ...
Page 155: ...ADV100 Block Diagrams 155 Multireference ...
Page 156: ...156 ADV100 Block Diagrams Motorpotentiometer Jog function ...
Page 157: ...ADV100 Block Diagrams 157 Monitor function ...
Page 158: ...158 ADV100 Block Diagrams ...
Page 159: ...ADV100 Block Diagrams 159 Commands ...
Page 160: ...160 ADV100 Block Diagrams ...
Page 161: ...ADV100 Block Diagrams 161 Digital inputs Digital outputs ...
Page 162: ...162 ADV100 Block Diagrams Analog inputs ...
Page 163: ...ADV100 Block Diagrams 163 Analog outputs Encoder config ...
Page 164: ...164 ADV100 Block Diagrams Speed reg gains ...
Page 165: ...ADV100 Block Diagrams 165 Torque config ...
Page 166: ...166 ADV100 Block Diagrams VF parameters ...
Page 167: ...ADV100 Block Diagrams 167 Functions ...
Page 168: ...168 ADV100 Block Diagrams ...
Page 169: ...ADV100 Block Diagrams 169 ...
Page 170: ...170 ADV100 Block Diagrams PID application ...
Page 171: ......