ADV100 • Functions description and parameters list
123
26 – APPLICATION
This menu is designed to host two applications using the MDPlc program.
It will not be possible to use both applications simultaneously.
The
558 Application select
parameter in the DRIVE CONFIG menu must be used to select between the two possible
applications.
ADV100 PID HVAC application
REFERENCES
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
Mod
11000 Set point sel
ENUM
Disable PID
-1
4174
RWZ FVS
Parameter for selecting the PID input reference. If you select PID disabilit [-1] the ramp reference and thus the drive
speed depend on the standard selections in the REFERENCES menu. For the other selections the parameters in
the REFERENCES menu are modified so that the ramp reference corresponds to the value of the
PID output
[3700]
variable.
If you select
Digital Param
[0] the PID reference corresponds to the value of parameter 11002
Set point sel
. One of
the following values can be set:
-1
Disable PID
0
Digital Param
1600
Analog inp 1X
1650
Analog inp 2X
3700
PID output
3710
Pad 6
3712
Pad 7
3714
Pad 8
3716
Pad 9
3718
Pad 10
3720
Pad 11
3722
Pad 12
3724
Pad 13
3726
Pad 14
3728
Pad 15
3730
Pad 16
4024
FieldbusM->S1
4034
FieldbusM->S2
4044
FieldbusM->S3
4054
FieldbusM->S4
4064
FieldbusM->S5
4074
FieldbusM->S6
4084
FieldbusM->S7
4094
FieldbusM->S8
4104
FieldbusM->S9
4114
FieldbusM->S10
4124
FieldbusM->S11
4134
FieldbusM->S12
4144
FieldbusM->S13
4154
FieldbusM->S14
4164
FieldbusM->S15
4174
FieldbusM->S16
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
Mod
11002 Set point val
FLOAT
0
0
0
RW FVS
If parameter 11000
Set point val
is set to
Digital Param
[0] the PID input reference value can be written in this
parameter. For the other selections of parameter 11000
Set point val
this parameter displays the value of the cur-
rent reference, scaled according to parameters 11012
Signals full scale
and 11014
Signals offset
and to the unit of
Summary of Contents for SIEIDrive ADV100
Page 1: ... Functions description and parameters list SIEIDrive Field oriented vector AC Drive ADV100 ...
Page 28: ...28 ADV100 Functions description and parameters list Ramp freeze Ramp Output Motor speed ...
Page 152: ...152 ADV100 Block Diagrams F Block Diagrams System Diagrams Index Drive overview ...
Page 153: ...ADV100 Block Diagrams 153 References ...
Page 154: ...154 ADV100 Block Diagrams Ramps Braking ...
Page 155: ...ADV100 Block Diagrams 155 Multireference ...
Page 156: ...156 ADV100 Block Diagrams Motorpotentiometer Jog function ...
Page 157: ...ADV100 Block Diagrams 157 Monitor function ...
Page 158: ...158 ADV100 Block Diagrams ...
Page 159: ...ADV100 Block Diagrams 159 Commands ...
Page 160: ...160 ADV100 Block Diagrams ...
Page 161: ...ADV100 Block Diagrams 161 Digital inputs Digital outputs ...
Page 162: ...162 ADV100 Block Diagrams Analog inputs ...
Page 163: ...ADV100 Block Diagrams 163 Analog outputs Encoder config ...
Page 164: ...164 ADV100 Block Diagrams Speed reg gains ...
Page 165: ...ADV100 Block Diagrams 165 Torque config ...
Page 166: ...166 ADV100 Block Diagrams VF parameters ...
Page 167: ...ADV100 Block Diagrams 167 Functions ...
Page 168: ...168 ADV100 Block Diagrams ...
Page 169: ...ADV100 Block Diagrams 169 ...
Page 170: ...170 ADV100 Block Diagrams PID application ...
Page 171: ......