ADV100 • Functions description and parameters list
101
22.10 - FUNCTIONS/VF ENERGY SAVE
With V/f control, the Energy saving function automatically reduces the output voltage requested by the configured V/f
curve, making it possible to save energy without changing the speed of the motor.
The output voltage can be reduced for as long as it is possible to reduce the flux current without increasing the torque
current. If the output voltage is reduced too much the drive will be unable to maintain a constant motor speed.
If the Energy saving function is enabled, the output voltage is only reduced if the drive is in the drive ready condition
and the speed reference is within the following range:
25% of
Vf frequency
(par. 2408) < speed reference <
Vf frequency
(par. 2408)
When the speed ramp output is constant for a time that can be set in parameter 3324
Energysave delay
the Energy
saving function automatically reduces the output voltage. The output voltage reduction phase stops and is maintained
when the torque current moves out of the range configured in parameter 3326
Energysave trqband 1
.
In the low output voltage condition, if there is a change in the ramp input reference or in the load conditions bringing
the torque current outside the range set in parameter 3328
Energysave trqband 2
, the Energy saving function auto-
matically restores the output voltage.
The energy saving function attempts to reduce the output voltage to a fixed minimum limit that is 70% of the voltage
defined by the V/f curve.
Nota:
For increased energy saving, disable the function set in parameter 2404
Voltage torque boost
or reduce the boost set in
parameter 2402
Voltage boost gain
as these functions tend to maintain the flux current at a constant level rendering the
Energy saving function ineffective.
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
Mod
22.10.1 3320 Energysave enable
BIT
0
0
1
ERWZ _V_
This parameter enables the energy saving function
0
Enabled
1
Disabled
If set to
0
the energy saving function is disabled
If set to
1
the energy saving function is enabled
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
Mod
22.10.2 3322 Energysave spd band
rpm INT16
2
0
100
ERW _V_
This parameter is used to set a speed used to calculate a range around the ramp output. When the ramp reference
is inside this range it is constant and the ramp output has reached the steady state. The Energy saving function uses
this information to decide whether or not to apply the output voltage reduction.
This parameter can be changed if there are small, continuous changes in the speed of the speed reference to avoid
continuously entering/leaving the output voltage reduction condition.
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
Mod
22.10.3 3324 Energysave delay
s
FLOAT
3.0
0.1
120.0
ERW _V_
This parameter is used to set the delay, once the speed set point has been reached, before starting to reduce the
output voltage.
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
Mod
22.10.4 3326 Energysave trqband 1
perc FLOAT
10.0
0.0
100.0
ERWS _V_
This parameter is used to set a percentage used to calculate a range around the torque current the moment the
output voltage starts to be reduced.
The torque current value is saved the moment the voltage starts to be reduced. if the torque current is not within the
calculated range during the output voltage reduction phase, output voltage reduction is aborted.
Summary of Contents for SIEIDrive ADV100
Page 1: ... Functions description and parameters list SIEIDrive Field oriented vector AC Drive ADV100 ...
Page 28: ...28 ADV100 Functions description and parameters list Ramp freeze Ramp Output Motor speed ...
Page 152: ...152 ADV100 Block Diagrams F Block Diagrams System Diagrams Index Drive overview ...
Page 153: ...ADV100 Block Diagrams 153 References ...
Page 154: ...154 ADV100 Block Diagrams Ramps Braking ...
Page 155: ...ADV100 Block Diagrams 155 Multireference ...
Page 156: ...156 ADV100 Block Diagrams Motorpotentiometer Jog function ...
Page 157: ...ADV100 Block Diagrams 157 Monitor function ...
Page 158: ...158 ADV100 Block Diagrams ...
Page 159: ...ADV100 Block Diagrams 159 Commands ...
Page 160: ...160 ADV100 Block Diagrams ...
Page 161: ...ADV100 Block Diagrams 161 Digital inputs Digital outputs ...
Page 162: ...162 ADV100 Block Diagrams Analog inputs ...
Page 163: ...ADV100 Block Diagrams 163 Analog outputs Encoder config ...
Page 164: ...164 ADV100 Block Diagrams Speed reg gains ...
Page 165: ...ADV100 Block Diagrams 165 Torque config ...
Page 166: ...166 ADV100 Block Diagrams VF parameters ...
Page 167: ...ADV100 Block Diagrams 167 Functions ...
Page 168: ...168 ADV100 Block Diagrams ...
Page 169: ...ADV100 Block Diagrams 169 ...
Page 170: ...170 ADV100 Block Diagrams PID application ...
Page 171: ......