130
ADV100 • Functions description and parameters list
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
Mod
11072 Const press thr time
sec
FLOAT
0.00
0.00
100000
RW FVS
This parameter defines the time for detecting that the constant pressure threshold has been exceeded. When the
error is below “
Const pressure thr
” for longer than “
Const press thr time
” the drive decelerates until it stops and
then moves to the “
Const pressure
” condition.
Example: suppose parameter 11002
Set point val
of a pump pressure control is 10 bar, parameter 11070
Const
pressure thr
is set to 5% and parameter 11072
Const press thr time
is set to 15 seconds.
This means that the error threshold is 0.5 bar (10 bar X 5% = 0.5 bar), so that when the feedback value is more than
9.5 bar for more than 15 seconds, the drive decelerates until it stops. When the feedback value is less than 9.5 bar,
the drive restarts.
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
Mod
11074 Const press offset
%
INT32
0
0
50
RW FVS
This parameter defines the offset (expressed as a percentage with respect to the set point) for moving from the con-
stant pressure condition and restarting the drive.
If the PID is in the constant pressure condition, to restart the drive the error must be higher than the value set in
parameter 11070
Const pressure thr
+ parameter 11074
Const press offset
.
Example: suppose the value of a pump pressure control set point (PAR 11002) is 10 bar, 11070
Const pressure thr
is set to 5%, PAR 11074
Const press offset
is set to 4%.
This means that to move to the constant pressure condition the feedback must be more than 9.5 bar. To restart the
drive the feedback must be less than 9.1 bar (10 – (10bar X 5% + 10bar X 4%)).
11074
(2)
(1)
(3)
(1) Set point
(2) Feedback value
(3) Offset level of liquid leakage
This parameter is used to avoid frequent start/stop operations due to leakages.
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
Mod
11076 Fluid loss thr
%
FLOAT
0.0
0.0
100.0
RW FVS
This parameter defines the threshold (expressed as a percentage with respect to the set point) for a change in the
error in the time set in PAR 11078 Fluid loss thr time to detect a leakage and move from the constant pressure condi-
tion and restart the drive.
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
Mod
11078 Fluid loss thr time
%
FLOAT
0.10
0.01
10.00
RW FVS
This parameter defines the time for calculating the change in PIDerror to detect the leakage.
Note:
If parameter 11076
Fluid loss thr
= 0 the function is not enabled.
To move from the constant pressure condition, the function is enabled if the PID error is higher than the value set in PAR
11070
Const pressure thr
otherwise each restart operation would correspond to an immediate stop with the return to the
constant pressure condition.
Summary of Contents for SIEIDrive ADV100
Page 1: ... Functions description and parameters list SIEIDrive Field oriented vector AC Drive ADV100 ...
Page 28: ...28 ADV100 Functions description and parameters list Ramp freeze Ramp Output Motor speed ...
Page 152: ...152 ADV100 Block Diagrams F Block Diagrams System Diagrams Index Drive overview ...
Page 153: ...ADV100 Block Diagrams 153 References ...
Page 154: ...154 ADV100 Block Diagrams Ramps Braking ...
Page 155: ...ADV100 Block Diagrams 155 Multireference ...
Page 156: ...156 ADV100 Block Diagrams Motorpotentiometer Jog function ...
Page 157: ...ADV100 Block Diagrams 157 Monitor function ...
Page 158: ...158 ADV100 Block Diagrams ...
Page 159: ...ADV100 Block Diagrams 159 Commands ...
Page 160: ...160 ADV100 Block Diagrams ...
Page 161: ...ADV100 Block Diagrams 161 Digital inputs Digital outputs ...
Page 162: ...162 ADV100 Block Diagrams Analog inputs ...
Page 163: ...ADV100 Block Diagrams 163 Analog outputs Encoder config ...
Page 164: ...164 ADV100 Block Diagrams Speed reg gains ...
Page 165: ...ADV100 Block Diagrams 165 Torque config ...
Page 166: ...166 ADV100 Block Diagrams VF parameters ...
Page 167: ...ADV100 Block Diagrams 167 Functions ...
Page 168: ...168 ADV100 Block Diagrams ...
Page 169: ...ADV100 Block Diagrams 169 ...
Page 170: ...170 ADV100 Block Diagrams PID application ...
Page 171: ......