ADV100 • Functions description and parameters list
23
B)
Decrease in the reference by values above
Par. 630
Par.630
= 300 rpm (prohibited speed threshold)
Par.632
= 10 rpm (thus tolerance band: 290 rpm…310 rpm)
Set speed reference = 305 rpm
Output frequency = 310 rpm
Set speed reference = 295 rpm
Output frequency = 310 rpm
The user can thus set any reference value, but if the set value is within the prohibited range, the drive automatically
maintains the speed outside the limits defined by the tolerance band.
During ramp phases the prohibited speed is passed freely and there are no points of discontinuity in the generation
of the output frequency.
The speed reference supplies the desired speed to the drive, which directly follows the reference pattern. This only
happens when the available torque is sufficient. In this case the drive functions at its current limit, until reaching the
set speed. The speed reference value determines the motor speed value. The sign determines the direction of rota-
tion.
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
Mod
5.15
640
Dig speed ref 1
rpm INT16 16/32
0
CALCI
CALCI
ERW FVS
5.16
642
Dig speed ref 2
rpm INT16 16/32
0
CALCI
CALCI
ERW FVS
Setting of the digital speed references. The overall speed reference is the result of the sum of the values with the
respective signs, of
Dig speed ref 1
and
Dig speed ref 2
. The digital speed references are linked to the ramp circuit
output.
The overall speed reference is the result of the sum of the values, with sign, of
Speed ref 1
and
Speed ref 2
.
Example 1:
Speed ref 1
= + 500 rpm
Speed ref 2
= + 300 rpm
Speed ref
= 500 rpm + 300 rpm = 800 rpm
Example 2:
Speed ref 1
= + 400 rpm
Speed ref 2
= - 600 rpm
Speed ref
= 400 rpm – 600 rpm = - 200 rpm
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
Mod
5.17
650
Speed ref 1 src
LINK 16/32
640
0
16384
ERW FVS
5.18
652
Speed ref 2 src
LINK 16/32
642
0
16384
ERW FVS
Selection of the origin (source) of the drive speed reference signals. The values that can be used as speed refer-
ences can be selected from those listed in the “
L_MLTREF
” selection list.
Summary of Contents for SIEIDrive ADV100
Page 1: ... Functions description and parameters list SIEIDrive Field oriented vector AC Drive ADV100 ...
Page 28: ...28 ADV100 Functions description and parameters list Ramp freeze Ramp Output Motor speed ...
Page 152: ...152 ADV100 Block Diagrams F Block Diagrams System Diagrams Index Drive overview ...
Page 153: ...ADV100 Block Diagrams 153 References ...
Page 154: ...154 ADV100 Block Diagrams Ramps Braking ...
Page 155: ...ADV100 Block Diagrams 155 Multireference ...
Page 156: ...156 ADV100 Block Diagrams Motorpotentiometer Jog function ...
Page 157: ...ADV100 Block Diagrams 157 Monitor function ...
Page 158: ...158 ADV100 Block Diagrams ...
Page 159: ...ADV100 Block Diagrams 159 Commands ...
Page 160: ...160 ADV100 Block Diagrams ...
Page 161: ...ADV100 Block Diagrams 161 Digital inputs Digital outputs ...
Page 162: ...162 ADV100 Block Diagrams Analog inputs ...
Page 163: ...ADV100 Block Diagrams 163 Analog outputs Encoder config ...
Page 164: ...164 ADV100 Block Diagrams Speed reg gains ...
Page 165: ...ADV100 Block Diagrams 165 Torque config ...
Page 166: ...166 ADV100 Block Diagrams VF parameters ...
Page 167: ...ADV100 Block Diagrams 167 Functions ...
Page 168: ...168 ADV100 Block Diagrams ...
Page 169: ...ADV100 Block Diagrams 169 ...
Page 170: ...170 ADV100 Block Diagrams PID application ...
Page 171: ......