ADV100 • Functions description and parameters list
33
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
Mod
8.1
870
Mpot setpoint
rpm INT16 16/32
0
CALCI
CALCI
R
FVS
The speed reference value of the Motor potentiometer function is displayed.
Enter this parameter to send the UP and DOWN commands from the keypad.
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
Mod
8.2
872
Mpot acceleration
s
FLOAT
5.0
0.01
1000.00
RW FVS
8.3
874
Mpot deceleration
s
FLOAT
5.0
0.01
1000.00
RW FVS
Setting of the acceleration/deceleration ramp times (in seconds) used with the Motor potentiometer function.
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
Mod
8.4
876
Mpot top lim
rpm INT16
1500
CALCI
CALCI
ERW FVS
Setting of the top limit for the speed reference output from the motor potentiometer.
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
Mod
8.5
878
Mpot bottom limit
rpm INT16
0
CALCI
CALCI
ERW FVS
Setting of the bottom limit for the speed reference output from the motor potentiometer.
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
Mod
8.6
880
Mpot init cfg
ENUM
Zero
0
3
ERW FVS
Use this parameter to configure the output value of the Motor potentiometer at drive start-up.
0
Last power off
1
Zero
2
Lower Limit
3
Upper Limit
When set to
Last power off
, the motor potentiometer output starts from the last frequency that was set before the
drive was switched off.
When set to
Zero
the motor potentiometer output starts from a value of 0.
When set to
Lower limit
the output of the motor potentiometer starts from the value of the lower limit set in the
Mpot
bottom limit
parameter.
When set to
Upper limit
the output of the motor potentiometer starts from the value of the upper limit set in the
Mpot
top limit
parameter.
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
Mod
8.7
882
Mpot preset cfg
ENUM
None
0
11
ERW FVS
This parameter can be used to configure the preset of the Motor potentiometer function, i.e. to configure the value at
which the Motor potentiometer input and output are set when the Preset command is enabled.
The Preset command has priority over the Up command and the Down command.
Mpot mode
(PAR 892) = [1]
Ramp&Follow
has priority over the Preset command, i.e. actions programmed with
Mpot preset cfg
(PAR 882) are not executed.
The Up and Down commands are enabled again when the Preset command is disabled.
0
None
1
Input = 0
2
Input = low lim
3
Input & ref = 0
4
Input & ref = low lim
5
Output = 0
6
Output = low lim
7
Output & ref = 0
Summary of Contents for SIEIDrive ADV100
Page 1: ... Functions description and parameters list SIEIDrive Field oriented vector AC Drive ADV100 ...
Page 28: ...28 ADV100 Functions description and parameters list Ramp freeze Ramp Output Motor speed ...
Page 152: ...152 ADV100 Block Diagrams F Block Diagrams System Diagrams Index Drive overview ...
Page 153: ...ADV100 Block Diagrams 153 References ...
Page 154: ...154 ADV100 Block Diagrams Ramps Braking ...
Page 155: ...ADV100 Block Diagrams 155 Multireference ...
Page 156: ...156 ADV100 Block Diagrams Motorpotentiometer Jog function ...
Page 157: ...ADV100 Block Diagrams 157 Monitor function ...
Page 158: ...158 ADV100 Block Diagrams ...
Page 159: ...ADV100 Block Diagrams 159 Commands ...
Page 160: ...160 ADV100 Block Diagrams ...
Page 161: ...ADV100 Block Diagrams 161 Digital inputs Digital outputs ...
Page 162: ...162 ADV100 Block Diagrams Analog inputs ...
Page 163: ...ADV100 Block Diagrams 163 Analog outputs Encoder config ...
Page 164: ...164 ADV100 Block Diagrams Speed reg gains ...
Page 165: ...ADV100 Block Diagrams 165 Torque config ...
Page 166: ...166 ADV100 Block Diagrams VF parameters ...
Page 167: ...ADV100 Block Diagrams 167 Functions ...
Page 168: ...168 ADV100 Block Diagrams ...
Page 169: ...ADV100 Block Diagrams 169 ...
Page 170: ...170 ADV100 Block Diagrams PID application ...
Page 171: ......