46 • Chapter 4 Wiring Procedure
ARTDrive V2 series - Instruction Manual
Table 4.3.1.3: Jumpers on Regulation Card RV33
Designation
Function
Factory setting
S0
The setting must not be changed
OFF
S1
The setting must not be changed
ON
S3
Factor
y
use, the setting must not be changed
-
S5 - S6
Terminating resistor for the serial interface RS485
ON (*)
ON= Termination resistor IN
OFF= No termination resistor
S8
Adaptation to the input signal of analog input 1 (terminals 1 and 2)
OFF
ON=0...20 mA / 4...20 mA
OFF=0...10 V / -10...+10 V
S9
Adaptation to the input signal of analog input 2 (terminals 3 and 4)
OFF
ON=0...20 mA / 4...20 mA
OFF=0...10 V / -10...+10 V
S10
Adaptation to the input signal of analog input 3 (terminals 5 and 6)
OFF
ON=0...20 mA / 4...20 mA
OFF=0...10 V / -10...+10 V
S11 - S12 - S13
Encoder setting ( jumpers on kit EAM_1618 supplied with the drive)
OFF
S14 - S15 - S16
ON=Sinusoidal SE or SESC encoder
(**)
OFF=Digital DE or DEHS encoder
S17
Monitoring of the C-channel of the digital encoder
OFF
(**)
ON=C-Channel monitored
OFF=C-Channel not monitored (required for single-ended channels)
S18 - S19
Encoder setting
B
S20 - S21
Pos. B=digital DEHS encoder
(**)
Pos. A= sinusoidal SESC encoder
S22 - S23
Analog input 3 enabling (alternative with SESC encoder)
B
(**)
Pos. A= if SESC encoder is used
Pos. B=analog input 3 enabled
Pos. OFF= resolver
S24
Jumper to disconnect 0 V (of 24 V) from ground
ON
ON=0 V connected to ground
OFF=0 V disconnected from ground
S25
Jumper to disconnect 0 V (regulation section) from ground
ON
ON=0 V connected to ground
OFF=0 V disconnected from ground
S26 - S27 (**)
Resover use enabling
ON
Pos. ON=when resolver is not used
Pos. OFF=resolver
S28
Encoder Internal power suppl
y
selection
ON / ON = +5 V
OFF / OFF = +8 V
ON/ON
S29
Internal use
A
S30
Second encoder qualifier input
A=from EXP-… board
B=from digital input "6" on RV33-3
A
a
y
4060
N
OTES
!
(*) on multidrop connection the jumper must be ON only for the last drop of a
serial line.
(**) see table 3.4.2.2 for more details on S11 ... S23 jumper settings.
The devices are factory set accordingly.
When fitting a regulation card as a spare, remember to set again the
encoders jumpers.
Summary of Contents for ARTDrive Vector V2 400Vac Series
Page 1: ...Instruction Manual ARTDrive ARTDrive Vector AC Drives V2 series 400Vac Class 575Vac Class...
Page 14: ...0 14 Chapter 0 Safety Precautions ARTDrive V2 series Instruction manual...
Page 40: ...40 Chapter 3 Installation Guidelines ARTDrive V2 series Instruction Manual...
Page 92: ...92 Chapter 5 Quick Start Up Guide ARTDrive V2 series Instruction Manual...
Page 358: ...358 Chapter 8 Appendix ARTDrive V2 series Instruction Manual...
Page 376: ...Chapter 9 Pick Lists 376 ARTDrive V2 series Instruction manual...