ARTDrive V2 series - Instruction Manual
Chapter 6 Parameter • 253
L03.01 DS restart time
[ms]
RWS
1000
0/30000
PP
V-F-S-B
Full
9047
IGBT desaturation restart time.
L04 ALARM CFG / Inst IOC
It trips when the IGBT instantaneous overcurrent is detected by output current sensor.
L04.00 IOC restart
N/A
RWS
0
0/1
DP
V-F-S-B
Easy 9063
Instantaneous overcurrent restart:
[0] off
[1] on
L04.01 IOC restart time
[ms]
RWS
1000
0/30000
PP
V-F-S-B
Easy 9064
Instantaneous overcurrent restart time.
L05 ALARM CFG / Ground
It trips when the output phase discharge to ground: Ground fault
L05.00 GF activity
N/A
RWS
2
1/6
DP
V-F-S-B
Easy 9640
Ground fault activity:
[1] Ignore
[2] Warning
[3] Disable drive
[4] Stop
[5] Fast stop
[6] Curr limstp
L05.01 GF threshold
[A]
RWS
D.Size
Calc/D.Size
PP
V-F-S-B
Easy 9641
Ground fault threshold
L06 ALARM CFG / EF cfg
It trips when the External fault input is active.
L06.00 EF src
N/A
RWS
Ipa4000 PList 3
PIN
V-F-S-B
Easy 9075
Ipa 4000 NULL = Default
It allows to connect the External fault input terminal strip.
ª
ª
ª
ª
ª
Pick List 3
Summary of Contents for ARTDrive Vector V2 400Vac Series
Page 1: ...Instruction Manual ARTDrive ARTDrive Vector AC Drives V2 series 400Vac Class 575Vac Class...
Page 14: ...0 14 Chapter 0 Safety Precautions ARTDrive V2 series Instruction manual...
Page 40: ...40 Chapter 3 Installation Guidelines ARTDrive V2 series Instruction Manual...
Page 92: ...92 Chapter 5 Quick Start Up Guide ARTDrive V2 series Instruction Manual...
Page 358: ...358 Chapter 8 Appendix ARTDrive V2 series Instruction Manual...
Page 376: ...Chapter 9 Pick Lists 376 ARTDrive V2 series Instruction manual...