![GEFRAN-SIEI ARTDrive Vector V2 400Vac Series Instruction Manual Download Page 131](http://html1.mh-extra.com/html/gefran-siei/artdrive-vector-v2-400vac-series/artdrive-vector-v2-400vac-series_instruction-manual_2205769131.webp)
Index
MENU
MENU
MENU
MENU
MENU
[Unit] Access Default
Min/Max
Format Reg.Mode Level Ipa
Parameter Name
Description
ARTDrive V2 series - Instruction Manual
Chapter 6 Parameter • 131
C00.24 Stop key mode
N/A
RWS
(*)
0/1
DP
V-F-S-B
Easy 3998
Stop key configuration (valid for Command select
≠
[I-O] keys only) :
[0] Inactive
(*): Default for Europe
Standard configuration, where main commands are coming from keypad.
Therefore, the STOP key will cause a normal stop of the motor.
[1] EmgStop & Al
(*): Default for American
Pressing the Stop key, the motor will execute an Emergency stop, following
the ramp programmed by Fast Stop deceleration time selected. After the
speed reaches the zero, the drive will trip with the dedicated alarm “Key Em
Stp fault”. An alarm reset will be needed to restore drive operations.
RU
N/ST
O
P
f
r
om p
r
og
r
amm
e
d
s
ou
r
c
e
ST
O
P KEY
Moto
r
Sp
ee
d
Ala
r
m
Re
s
e
t
Ala
r
m Signal
Figure C00.24: Stop Key Mode sequences
C00.25 FRC cmd mode
N/A
RWS
(*)
0/2
DP
V-F-S-B
Easy 8087
Definition of Forward Reverse Control inverter commands:
[0] Normal
(*): Default for Europe. FRC (Forward Reverse Control) function as standard: it
allows a protection in case of a sudden failure of the Forward or Reverse
command, therefore a protection on the rotation direction. The Block has two
inputs, Forward src and Reverse src, and two outputs FRC invers and FRC
alarm. The output can be connected where necessary, for example on the
Ramp or Speed Blocks.
[1] Two wires
(*): Default for American. 2-Wires control commands
[2] Three wires
3-Wires control commands
N
OTE
!
To activate 2-Wires or 3-Wires control, the following parameters have to be set:
C00.00 - Term StrStp src = FRC str mon (Ipa 8086)
D00.03 - Ramp ref inv src = FRC reverse (Ipa 8081)
Summary of Contents for ARTDrive Vector V2 400Vac Series
Page 1: ...Instruction Manual ARTDrive ARTDrive Vector AC Drives V2 series 400Vac Class 575Vac Class...
Page 14: ...0 14 Chapter 0 Safety Precautions ARTDrive V2 series Instruction manual...
Page 40: ...40 Chapter 3 Installation Guidelines ARTDrive V2 series Instruction Manual...
Page 92: ...92 Chapter 5 Quick Start Up Guide ARTDrive V2 series Instruction Manual...
Page 358: ...358 Chapter 8 Appendix ARTDrive V2 series Instruction Manual...
Page 376: ...Chapter 9 Pick Lists 376 ARTDrive V2 series Instruction manual...