52 • Chapter 4 Wiring Procedure
ARTDrive V2 series - Instruction Manual
4.4 Serial Interface
4.4.1 Serial Interface Description
The RS 485 serial interface enables data transfer via a loop made of two
symmetrical, twisted conductors with a common shield. The maximum
transmission distance is 1200 m (3936 feet) with a transfer rate of 9.6 KBaud.
The transmission is carried out via a differential signal. RS 485 interfaces are
bus-compatible in half-duplex mode, i.e. sending and receiving take place in
sequence. Up to 31 AVy devices (up to 128 address selectable) can be networked
together via the RS 485 interface. Address setting is carried out via the
M00.00
- Slave address
parameter (
COM / RS485
menu).
The serial protocol can be set via
M00.02 - Protocol type
parameter (
COM /
RS485
menu), which allows to set following types: SLINK 4 (default), Modbus
RTU and Jbus.
1
2
3
4
5
9
8
7
6
150 R
TxA/RxA
TxB/RxB
0 V S
+5 V S
S5
S6
PE
RS485
XS
100
R
470
R
470
R
+5 V
Figure 4.4.1.1: RS485 Serial Interface
The RS 485 on the AVy series device is located on the Regulation card in the
form of a 9-pole SUB-D socket connector (XS).The communication may be with
or without galvanic isolation: by using galvanic isolation an external power supply
is necessary (+5V). Communication without galvanic isolation are suggested
only if making a temporary connection to one drive. The differential signal is
transferred via PIN 3 (TxA/RxA) and PIN 7 (TxB/RxB). Bus terminating resistors
must be connected at the physical beginning and end of an RS 485 bus in order
to prevent signal reflexion. The bus terminating resistors on AVy series devices
are connected via jumpers S5 and S6. This enables a direct point-to-point
connection with a PLC or PC.
N
OTE
!
Ensure that only the first and last drop of an RS 485 bus have a bus terminating
resistor (S5 and S6 mounted). In all other cases (within the line) jumpers S5
and S6 must not be mounted.
Summary of Contents for ARTDrive Vector V2 400Vac Series
Page 1: ...Instruction Manual ARTDrive ARTDrive Vector AC Drives V2 series 400Vac Class 575Vac Class...
Page 14: ...0 14 Chapter 0 Safety Precautions ARTDrive V2 series Instruction manual...
Page 40: ...40 Chapter 3 Installation Guidelines ARTDrive V2 series Instruction Manual...
Page 92: ...92 Chapter 5 Quick Start Up Guide ARTDrive V2 series Instruction Manual...
Page 358: ...358 Chapter 8 Appendix ARTDrive V2 series Instruction Manual...
Page 376: ...Chapter 9 Pick Lists 376 ARTDrive V2 series Instruction manual...