FUNCTION / Power loss ctrl
N
OTE
!
Menu accessible with Access Level = FULL.
The Function allows to control a power loss or a break of the Mains voltage.
In the configurations, via the
I01.00 - PL function sel
parameter, it is possible to set
several methods to control a possible power loss:
[0] Off
Function is not active
[1] PL stop
It is a controlled stop during which, through the energy recovered from the
load, the motor is constantly controlled.
The DC link voltage is controlled in order to be kept closed to the
I03.12 - PLS Vdc ref
reference (internal value, it is usually closed to the
Overvoltage voltage).
In this case the aim is to try to perform a controlled stop of the machine.
The control variable is the torque current limit.
[2] PL ridethru
With this setting it is possible to let the motor shaft rotate as long as
possible during some Mains holes.
The DC link voltage is controlled in order to be kept slightly higher than
the Undervoltage threshold, thus minimizing the losses. In this case the
Mains hole is considered to be temporary and a crossing attempt is
performed.
The control variable is an additional reference for the torque current
(negative).
A signal,
I01.21 - PL next fact
, supplies the ratio between the motor speed and the speed
reference. By connecting it to the speed ratio of the slave drive, it is possible to obtain the
line synchronism.
N
OTE
!
This function is not active in case of a functioning condition with a 230Vmain
voltage.
I01
FUNCTION / PwrL ctrl
I01.00 PL function sel
N/A
RWSZ 0
0/2
DV
V-F-S-B
Full
2300
It allows to make a selection among the PL stop, PL ridethru and Off function.
This function has to be enabled only on the line Master drive:
[0] Off
[1] PL stop
[2] PL ridethru
I01.10 PL acceleration
[rpm/s] RWS
100
1/Calc
PV
V-F-S-B
Full
2302
Setting of the acceleration time when the powerloss stop function is active (standard 100
rpm/s).
Summary of Contents for ARTDrive Vector V2 400Vac Series
Page 1: ...Instruction Manual ARTDrive ARTDrive Vector AC Drives V2 series 400Vac Class 575Vac Class...
Page 14: ...0 14 Chapter 0 Safety Precautions ARTDrive V2 series Instruction manual...
Page 40: ...40 Chapter 3 Installation Guidelines ARTDrive V2 series Instruction Manual...
Page 92: ...92 Chapter 5 Quick Start Up Guide ARTDrive V2 series Instruction Manual...
Page 358: ...358 Chapter 8 Appendix ARTDrive V2 series Instruction Manual...
Page 376: ...Chapter 9 Pick Lists 376 ARTDrive V2 series Instruction manual...