Maintenance
Maintenance plan
GE Information
08- 2016
L51- 004EN/07
2/8
Maintenance plan
Maintenance
frequency
Under normal operating conditions, the maintenance plan may be defined as
follows:
Type of
examination
Frequency
Comment
Maintenance
visits
(M1)
Once or twice a year
It is advisable to perform
at least 2 CO duty cycles
per year, when apparatus
are scarcely used, in order
to
check
that
the
circuit- breaker
and
associated
control
circuits
are
working
properly.
Inspections
(M2)
Every five years
This
necessitates
circuit- breaker shutdown. It
is not necessary, however to
dismantle
interrupting
chambers
and
other
sub- assemblies.
Overhaul
(M4)
Perform when one of the
following criteria is reached:
operating life time
20
years
number of mechanical
cycles
3,000
electric wear limit
However, it is recommended
to proceed with inspection of
the pole or circuit- breaker
used the most, then to adapt
the
maintenance
programme for the other
breakers depending on the
results observed.