Installation
Coupling of column and chambers
GE Information
L31- 7137EN/02
16/18
11- 2016
Final coupling,
continued
Connection
chambers/column
The table below shows the steps for connecting the chambers to the column:
Step
Action
Illustration
4
Slowly lower the column onto
the breaking chamber casing
(2).
Position the lugs (51) for the
corona shield (50) on the rim
of the column then attach
using bolts (21), washers (22)
and special nuts (23) - See
’
Locking Fixings
’.
See
module
’General
assembly procedures’.
Lock the nuts (23) at the
appropriate torque, immobil-
ising the bolt heads (21).
H M16- 65 (75)
13,5 daN.m
x 6
21
22
23
51
x 4
H M10- 30
3,2 daN.m
2
52
50
5
Tighten all fixings (52) to their
appropriate torque level.
6
End of coupling operation -
stop the timer and note the
time taken.
7
Remove the last section
(A)
and the nut (41) from the cent-
ring pins.
Fix the last bolts (21), wash-
ers (22) and special nuts (23)
referring to ”
Locking fix-
ings
”.
See
module
’General
assembly procedures’.
Lock the nuts (23) at the
appropriate torque, immobil-
ising the bolt heads (21).
H M16-65/75
13,5 daN.m
x 2
(A)
41
21
22
23
22
Continued on next page.
Summary of Contents for SF6
Page 206: ...Grid Solutions This page is intentionally blank...
Page 212: ...Grid Solutions This page is intentionally blank...
Page 216: ...Grid Solutions This page is intentionally blank...
Page 220: ...Grid Solutions This page is intentionally blank...
Page 299: ...GE Information This page is intentionally blank...
Page 300: ......