Installation
Filling with SF
6
gas
GE Information
07- 2016
L32- 007EN/07
8/8
Moisture content of SF
6
gas in circuit- breaker
Principle
This measurement is not required, the equipment being provided with molec-
ular sieves in sufficient quantity to give a dew point of
0
C (32
F) for an
ambient temperature of 20
C (68
F), this applies for a unit filled to its nominal
pressure for 2 or 3 months.