Installation
Erection general procedures
GE Information
07- 2016
L31- 003EN/04
3/4
Screw sealing
Introduction
To prevent humidity from penetrating SF
6
gaskets, the outer mounting screws
should be sealed by applying an appropriate product.
NOTE
: This procedure should be applied to all assemblages of parts
submitted to SF
6
pressure and electrical connection assembling.
Necessary products
List of the Grid Solutions products and accessories necessary for the screw
sealing :
Grid
Solutions
reference
Diagram
Designation
- 01818327
LOCTITE 225 (250ml)
- 01835265
MOLYKOTE 111 (100g tube)
- 01835118
CONTACTAL HPG (200g tube)
Choice of the
product to use
The table below gives the product to use for the screw sealing depending on
the assembling type :
If assembling...
Product to use ...
with seals
Can be
dismantled ?
Product ...
YES
MOLYKOTE 111
NO
LOCTITE 225
electrical connections
CONTACTAL HPG