Installation
Installation of stress- shields
on the interrupting chambers
GE Information
L31- 669EN/03
3/4
02- 2017
Installing stress- shields
Necessary
Grid Solutions
components
List of the Grid Solutions components necessary for the assembling (per
pole) :
Mark
Diagram
Designation
Number
(5)
Screws
H M12-30
8
Necessary product
LOCTITE 262 (screws locking)
Process
Install the stress- shields (1) at each end of the interrupting chambers (4)
using the screws (5).
NOTE
: Lock the screws (5) with “LOCTITE 262”.
1
x 4
H M10- 30
3,2 daN.m
5
x 4
H M12- 30
5 daN.m
5
1
1
4
4