Installation
Coupling of column and chambers
GE Information
L31- 7138EN/02
13/16
11- 2016
Final coupling,
continued
Connection
chambers/column
The table below shows the steps for connecting the chambers to the column:
Step
Action
Illustration
1
Clean the contact surfaces
”
A
” and ”
B
” with ISOPRO-
PANOL.
Only coat surface
”B”
with
MOLYKOTE M111 lubricant.
Remove the trolley stop fixing
screws (40).
40
A
B
2
Remove the screws (42) from
the centring pins.
42
42
3
Continue to slowly lower the
breaking chamber, removing
the first two sections of cent-
ring pin (30 & 31) when they
are no longer of any use as a
guide, in the following order:
- First section (C)
- Screw (42)
- Second section (B)
NOTE
: The aim of this
operation is to prevent the
centring pins coming into
contact with the porcelain
fins on the column.
30
31
(C)
(B)
(42)
Continued on next page.