6-8
L60 LINE PHASE COMPARISON SYSTEM – INSTRUCTION MANUAL
STATUS
CHAPTER 6: ACTUAL VALUES
6
The display shows both the current position and the full range. The current position only (an integer from 0 through 7) is the
actual value.
6.3.13 Flex States
ACTUAL VALUES
STATUS
FLEX STATES
There are 256 FlexState
TM
bits available. The second line value indicates the state of the given FlexState bit.
6.3.14 Ethernet
ACTUAL VALUES
STATUS
ETHERNET
These values indicate the status of the first, second, and third Ethernet links.
6.3.15 Real time clock synchronizing
ACTUAL VALUES
STATUS
REAL TIME CLOCK SYNCHRONIZING
RTC SYNC SOURCE
actual value is the time synchronizing source the relay is using at present. Possible sources are: Port 1
PTP Clock, Port 2 PTP Clock, Port 3 PTP Clock, IRIG-B, Other, and None, where "Other" means any less precise source (SNTP,
IEC 103, IEC 104, or DNP). An actual value displays when the relay includes the IEEE 1588 software option.
The
GRANDMASTER ID
is the grandmasterIdentity code being received from the present PTP grandmaster, if any. When the
relay is not using any PTP grandmaster, this actual value is zero. The grandmasterIdentity code is specified by PTP to be
globally unique, so one can always know which clock is grandmaster in a system with multiple grandmaster-capable
clocks.
FLEX STATES
PARAM 1: Off
Off
Range: On, Off
PARAM 256: Off
Off
Range: On, Off
ETHERNET
ETHERNET PRI LINK
STATUS: Fail
Range: Fail, OK
ETHERNET SEC LINK
STATUS: Fail
Range: Fail, OK
ETHERNET TER LINK
STATUS: Fail
Range: Fail, OK
REAL TIME CLOCK
SYNCHRONIZING
RTC SYNC SOURCE:
None
Range: see below
GRANDMASTER ID:
0X0000000000000000
Range: any 8 octet value
ACCURACY:
999999999 ns
Range: 0 to 999,999,999 ns
PORT 1 PTP STATE:
No Signal
Range: Disabled, No Signal, Calibrating, Synch’d (No
Pdelay), Synchronized
PORT 2 PTP STATE:
No Signal
Range: Disabled, No Signal, Calibrating, Synch’d (No
Pdelay), Synchronized
PORT 3 PTP STATE:
No Signal
Range: Disabled, No Signal, Calibrating, Synch’d (No
Pdelay), Synchronized
PTP - IRIG-B DELTA:
500000000 ns
Range: -500,000,000 to +500,000,000 ns