CHAPTER 5: SETTINGS
CONTROL ELEMENTS
L60 LINE PHASE COMPARISON SYSTEM – INSTRUCTION MANUAL
5-335
5
An additional condition is introduced to inhibit a fuse failure declaration when the monitored circuit is de-energized;
positive-sequence voltage and current are both below threshold levels.
VT FUSE FAILURE 1 FUNCTION
— Enables and disables the fuse failure feature for Source 1 VT Fuse Fail.
NEUTRAL WIRE OPEN 1 DETECTION
— Enables and disables the VT neutral wire open detection function. When the VT is
connected in Delta, do not enable this function because there is no neutral wire for Delta connected VT.
NEUTRAL WIRE OPEN 1 3 HRAM PKP
— Specifies the pickup level of 3rd harmonic of 3V0 signal for the
NEUTRAL WIRE OPEN
DETECTION
logic to pick up.
Base voltage for this element is
PHASE VT SECONDARY
setting in the case of WYE VTs and (
PHASE VT SECONDARY
)/
in case
of DELTA VTs. The setting is found under
SETTINGS
SYSTEM SETUP
AC INPUTS
VOLTAGE BANK
PHASE VT SECONDARY
.
Figure 5-192: VT fuse fail logic
5.7.9.7 Open pole detector
SETTINGS
CONTROL ELEMENTS
MONITORING ELEMENTS
OPEN POLE
OPEN POLE
OPEN POLE FUNCTION:
Disabled
Range: Disabled, Enabled
OPEN POLE BLOCK:
Off
Range: FlexLogic operand
OPEN POLE VOLTAGE
SUPV: Disabled
Range: Disabled, Enabled