CHAPTER 5: SETTINGS
FLEXLOGIC
L60 LINE PHASE COMPARISON SYSTEM – INSTRUCTION MANUAL
5-175
5
ELEMENT:
Disconnect switch
SWITCH 1 OFF CMD
SWITCH 1 ON CMD
SWITCH 1 CLOSED
SWITCH 1 OPEN
SWITCH 1 DISCREP
SWITCH 1 TROUBLE
SWITCH 1
Φ
A CLSD
SWITCH 1
Φ
A OPEN
SWITCH 1
Φ
A BAD ST
SWITCH 1
Φ
A INTERM
SWITCH 1
Φ
B CLSD
SWITCH 1
Φ
B OPEN
SWITCH 1
Φ
B BAD ST
SWITCH 1
Φ
B INTERM
SWITCH 1
Φ
C CLSD
SWITCH 1
Φ
C OPEN
SWITCH 1
Φ
C BAD ST
SWITCH 1
Φ
C INTERM
SWITCH 1 BAD STATUS
SWITCH 1 TAG ON
SWITCH 1 TAG OFF
SWITCH 1 SUBD CLSD
SWITCH 1 SUBD OPEN
SWITCH 1 BYPASS ON
SWITCH 1 BYPASS OFF
Disconnect switch 1 open command initiated
Disconnect switch 1 close command initiated
Disconnect switch 1 is closed
Disconnect switch 1 is open
Disconnect switch 1 has discrepancy
Disconnect switch 1 trouble alarm
Disconnect switch 1 phase A is closed
Disconnect switch 1 phase A is open
Disconnect switch 1 phase A bad status is detected (discrepancy between
the 89/a and 89/b contacts)
Disconnect switch 1 phase A intermediate status is detected (transition from
one position to another)
Disconnect switch 1 phase B is closed
Disconnect switch 1 phase B is open
Disconnect switch 1 phase B bad status is detected (discrepancy between
the 89/a and 89/b contacts)
Disconnect switch 1 phase B intermediate status is detected (transition from
one position to another)
Disconnect switch 1 phase C is closed
Disconnect switch 1 phase C is open
Disconnect switch 1 phase C bad status is detected (discrepancy between
the 89/a and 89/b contacts)
Disconnect switch 1 phase C intermediate status is detected (transition from
one position to another)
Disconnect switch 1 bad status is detected on any pole
Switch 1 tagged so manual trip and close is blocked
Switch 1 not tagged
Switch 1 status manually substituted to closed
Switch 1 status manually substituted to open
Switch 1 control interlocking is bypassed manually
Switch 1 control interlocking is not bypassed manually
SWITCH 2 to 8
Same set of operands as shown for SWITCH 1
ELEMENT:
Synchrocheck
SYNC1 DEAD S OP
SYNC1 DEAD S DPO
SYNC1 SYNC OP
SYNC1 SYNC DPO
SYNC1 CLS OP
SYNC1 CLS DPO
SYNC1 V1 ABOVE MIN
SYNC1 V1 BELOW MAX
SYNC1 V2 ABOVE MIN
SYNC1 V2 BELOW MAX
SYNC1 S-CLOSE OP
SYNC1 S-CLOSE OP DPO
SYNC1 S-CLOSE ARMD
Synchrocheck 1 dead source has operated
Synchrocheck 1 dead source has dropped out
Synchrocheck 1 in synchronization has operated
Synchrocheck 1 in synchronization has dropped out
Synchrocheck 1 close has operated
Synchrocheck 1 close has dropped out
Synchrocheck 1 V1 is above the minimum live voltage
Synchrocheck 1 V1 is below the maximum dead voltage
Synchrocheck 1 V2 is above the minimum live voltage
Synchrocheck 1 V2 is below the maximum dead voltage
Synchrocheck 1 S-CLOSE has operated
Synchrocheck 1 S-CLOSE has dropped out
Synchrocheck 1 S-CLOSE has been armed
SYNC 2 to 4
Same set of operands as shown for SYNC 1
ELEMENT:
Teleprotection
channel tests
TELEPRO CH1 FAIL
TELEPRO CH2 FAIL
TELEPRO CH1 ID FAIL
TELEPRO CH2 ID FAIL
TELEPRO CH1 CRC FAIL
TELEPRO CH2 CRC FAIL
TELEPRO CH1 PKT LOST
TELEPRO CH2 PKT LOST
Channel 1 failed
Channel 2 failed
The ID check for a peer relay on channel 1 has failed
The ID check for a peer relay on channel 2 has failed
CRC detected packet corruption on channel 1
CRC detected packet corruption on channel 2
CRC detected lost packet on channel 1
CRC detected lost packet on channel 2
ELEMENT:
Teleprotection
inputs/outputs
TELEPRO INPUT 1-1 On
↓
TELEPRO INPUT 1-16 On
TELEPRO INPUT 2-1 On
↓
TELEPRO INPUT 2-16 On
Flag is set, Logic =1
↓
Flag is set, Logic =1
Flag is set, Logic =1
↓
Flag is set, Logic =1
ELEMENT:
Thermal overload
protection
THERMAL PROT 1 PKP
THERMAL PROT 1 OP
Thermal overload protection 1 picked up
Thermal overload protection 1 operated
THERMAL PROT 2
Same set of operands as shown for THERMAL PROT 1
Operand type
Operand syntax
Operand description