5-56
L60 LINE PHASE COMPARISON SYSTEM – INSTRUCTION MANUAL
PRODUCT SETUP
CHAPTER 5: SETTINGS
5
The menu for the binary input points (DNP) or MSP points (IEC 60870-5-104) follows.
SETTINGS
PRODUCT SETUP
COMMUNICATIONS
DNP / IEC104 POINT LISTS
BINARY INPUT / MSP POINTS
Up to 256 binary input points can be configured for the DNP or IEC 60870-5-104 protocols. The points are configured by
assigning an appropriate FlexLogic operand. See the Introduction to FlexLogic section in this chapter for the range of
assignable operands.
Changes to the DNP / IEC 60870-5-104 point lists take effect when the L60 is restarted.
The menu for the analog input points (DNP) or MME points (IEC 60870-5-104) follows.
SETTINGS
PRODUCT SETUP
COMMUNICATIONS
DNP / IEC104 POINT LISTS
ANALOG INPUT / MME
POINTS
Up to 256 analog input points can be configured for the DNP or IEC 60870-5-104 protocols. The analog point list is
configured by assigning an appropriate FlexAnalog parameter to each point. See the FlexAnalog Parameters section in
Appendix A for the range of assignable parameters.
Changes to the DNP / IEC 60870-5-104 point lists take effect when the L60 is restarted.
5.3.5.12 IEC 61850 protocol
The IEC 61850 settings are accessible in EnerVista software or a substation configuration language (SCL) generating tool.
The path is
Settings > Product Setup > Communications > IEC 61850
or
Settings > IEC 61850
. The settings are not
accessible from the front panel of the device.
BINARY INPUT / MSP
POINTS
Point: 0
Off
Range: FlexLogic operand
Point: 1
Off
Range: FlexLogic operand
Point: 255
Off
Range: FlexLogic operand
ANALOG INPUT / MME
POINTS
Point: 0
Off
Range: any FlexAnalog parameter
Point: 1
Off
Range: any FlexAnalog parameter
Point: 255
Off
Range: any FlexAnalog parameter
The DNP / IEC 60870-5-104 point lists always begin with point 0 and end at the first “Off” value. Since DNP / IEC
60870-5-104 point lists must be in one continuous block, any points assigned after the first “Off” point are ignored.
The L60 is provided with optional IEC 61850 communications. This feature is specified as a software option at
the time of ordering. See the Order Codes section in chapter 2 for details.
IEC 61850 messaging can form part of protection schemes. Consider IEC 61850 settings with the same criticality as
protection element settings. To ensure reliable performance of protection schemes utilizing IEC 61850 messaging,
route IEC 61850 traffic on a separate port from SCADA communications, or use redundant, independent ports, and
a high-speed network recovery method, such as PRP.