CHAPTER 5: SETTINGS
OVERVIEW
L60 LINE PHASE COMPARISON SYSTEM – INSTRUCTION MANUAL
5-7
5
Table 5-1: Source configuration for phase comparison
5.2.2.2 CT/VT module configuration
CT and voltage transformer (VT) input channels are contained in CT/VT modules. The type of input channel can be phase/
neutral/other voltage, phase/ground current, or sensitive ground current. The CT/VT modules calculate total waveform
RMS levels, fundamental frequency phasors, symmetrical components, and harmonics for voltage or current, as allowed
by the hardware in each channel. These modules can calculate other parameters as directed by the CPU module.
A CT/VT module contains up to eight input channels, numbered 1 through 8. The channel numbering corresponds to the
module terminal numbering 1 through 8 and is arranged as follows. Channels 1, 2, 3, and 4 are always provided as a group,
hereafter called a “bank,” and all four are either current or voltage, as are channels 5, 6, 7, and 8. Channels 1, 2, 3 and 5, 6,
7 are arranged as phase A, B, and C respectively. Channels 4 and 8 are either another current or voltage.
Banks are ordered sequentially from the block of lower-numbered channels to the block of higher-numbered channels,
and from the CT/VT module with the lowest slot position letter to the module with the highest slot position letter, as follows.
The UR platform allows for a maximum of six sets of three-phase voltages and six sets of three-phase currents. The result
of these restrictions leads to the maximum number of CT/VT modules in a chassis to three. The maximum number of
sources is six. A summary of CT/VT module configurations is as follows.
5.2.2.3 CT/VT input channel configuration
Upon relay startup, configuration settings for every bank of current or voltage input channels in the relay are generated
automatically from the order code. Within each bank, a channel identification label is assigned automatically to each bank
of channels in a given product. The
bank
naming convention is based on the physical location of the channels, required by
the user to know how to connect the relay to external circuits. Bank identification consists of the letter designation of the
slot in which the CT/VT module is mounted as the first character, followed by numbers indicating the channel, either 1 or 5.
See the HardFiber instruction manual for designations of HardFiber voltage and current banks.
For three-phase channel sets, the number of the lowest numbered channel identifies the set. For example, F1 represents
the three-phase channel set of F1/F2/F3, where F is the slot letter and 1 is the first channel of the three channels.
Upon startup, the CPU configures the settings required to characterize the current and voltage inputs, and it displays them
in the appropriate section in the sequence of the banks (as described earlier) as follows for a maximum configuration: F1,
F5, L1, L5, S1, and S5.
Function
CT/VT module 1 (Type 8P)
CT/VT module 1 (Type 8F)
SRC 1
SRC 2
SRC 3
SRC 4
Phase current
F1 to F3 CT channels (used for
87PC first current and Breaker
Failure 1)
Not available
L1 to L3 CT channels (used for
87PC second current and
Breaker Failure 2). This source
is configurable only if a
second CT/VT module is
ordered.
Sum of F1:F3 and L1:L3 (used
for distance and overcurrent)
Ground current
F1 (Ground overcurrent)
Not available
---
---
Phase voltage
Not available
Not available
---
Three-phase line VT for
distance and synchrocheck
Auxiliary voltage Not available
Not available
Single-phase bus VT for
synchrocheck
---
Increasing slot position letter -->
CT/VT module 1
CT/VT module 2
CT/VT module 3
< bank 1 >
< bank 3 >
< bank 5 >
< bank 2 >
< bank 4 >
< bank 6 >
Item
Maximum number
CT/VT Module
2
CT Bank (3 phase channels, 1 ground channel)
2
VT Bank (3 phase channels, 1 auxiliary channel)
1