5-176
L60 LINE PHASE COMPARISON SYSTEM – INSTRUCTION MANUAL
FLEXLOGIC
CHAPTER 5: SETTINGS
5
ELEMENT:
Trip output
TRIP 3-POLE
TRIP 1-POLE
TRIP PHASE A
TRIP PHASE B
TRIP PHASE C
TRIP AR INIT 3-POLE
TRIP FORCE 3-POLE
TRIP OUTPUT OP
TRIP Z2PH TMR INIT
TRIP Z2GR TMR INIT
Trip all three breaker poles
A single-pole trip-and-reclose operation is initiated
Trip breaker pole A, initiate phase A breaker fail and reclose
Trip breaker pole B, initiate phase B breaker fail and reclose
Trip breaker pole C, initiate phase C breaker fail and reclose
Initiate a three-pole reclose
Three-pole trip must be initiated
Any trip is initiated by the trip output
Phase distance zone 2 timer is initiated by the trip output
Ground distance zone 2 timer is initiated by the trip output
ELEMENT:
Trip bus
TRIP BUS 1 PKP
TRIP BUS 1 OP
Asserted when the trip bus 1 element picks up
Asserted when the trip bus 1 element operates
TRIP BUS 2 to 6
Same set of operands as shown for TRIP BUS 1
ELEMENT:
Wattmetric zero-
sequence directional
WATTMETRIC 1 PKP
WATTMETRIC 1 OP
Wattmetric directional element 1 has picked up
Wattmetric directional element 1 has operated
WATTMETRIC 2
Same set of operands as per WATTMETRIC 1
FIXED OPERANDS
Off
Logic = 0. Does nothing and can be used as a delimiter in an equation list;
used as ‘Disable’ by other features.
On
Logic = 1. Can be used as a test setting.
INPUTS/OUTPUTS:
Contact inputs
Cont Ip 1 On
Cont Ip 2 On
↓
Cont Ip 1 Off
Cont Ip 2 Off
↓
Cont Ip 120 On
Cont Ip 120 Off
(does not appear unless ordered)
(does not appear unless ordered)
↓
(does not appear unless ordered)
(does not appear unless ordered)
↓
(does not appear unless ordered)
(does not appear unless ordered)
INPUTS/OUTPUTS:
Contact outputs,
current
(from detector on
form-A output only)
Cont Op 1 IOn
Cont Op 2 IOn
↓
Cont Op 72 IOn
(does not appear unless ordered)
(does not appear unless ordered)
↓
(does not appear unless ordered)
INPUTS/OUTPUTS:
Contact outputs,
voltage
(from detector on
form-A output only)
Cont Op 1 VOn
Cont Op 2 VOn
↓
Cont Op 72 VOn
(does not appear unless ordered)
(does not appear unless ordered)
↓
(does not appear unless ordered)
Cont Op 1 VOff
Cont Op 2 VOff
↓
Cont Op 72 VOff
(does not appear unless ordered)
(does not appear unless ordered)
↓
(does not appear unless ordered)
INPUTS/OUTPUTS:
Direct inputs
DIRECT INPUT 1 On
↓
DIRECT INPUT 32 On
Flag is set, logic=1
↓
Flag is set, logic=1
INPUTS/OUTPUTS:
RxGOOSE DPS
RxG DPS 1 BAD
RxG DPS 1 INTERM
RxG DPS 1 OFF
RxG DPS 1 ON
Asserted while the RxGOOSE double-point status input is in the bad state
Asserted while the RxGOOSE double-point status input is in the intermediate
state
Asserted while the RxGOOSE double-point status input is off
Asserted while the RxGOOSE double-point status input is on
RxG DPS 2 to 5
Same set of operands as per RxG DPS 1
INPUTS/OUTPUTS:
RxGOOSE Booleans
RxG Bool 1 On
RxG Bool 2 On
RxG Bool 3 On
↓
RxG Bool 256 On
Flag is set, logic=1
Flag is set, logic=1
Flag is set, logic=1
↓
Flag is set, logic=1
INPUTS/OUTPUTS:
Virtual inputs
Virt Ip 1 On
Virt Ip 2 On
Virt Ip 3 On
↓
Virt Ip 64 On
Flag is set, logic=1
Flag is set, logic=1
Flag is set, logic=1
↓
Flag is set, logic=1
Operand type
Operand syntax
Operand description