2-25
Chapter 2
3. Function Explanation
2
■
E43 LED Monitor (Function)
■
E44 LED Monitor (Display at STOP mode)
The data during inverter operation, during stopping, at
frequency setting, and at PID setting is displayed on the LED
monitor.
Display during running and stopping
During running, the items selected in “E43 LED Monitor
(Function),” are displayed. In “E44 LED Monitor (Display at
STOP mode),” specify whether to display some items out of
the set values or whether to display the same items as during
running.
NOTE:
Value set
E44=0
E44=1
to E43
Stopping
Running
Stopping
Running
0
Output frequency (before slip
compensation) (Hz)
1
Output frequency (after slip compen-
sation) (Hz)
2
Set frequency value (Hz)
3
Output current (A)
4
Output voltage (command value) (V)
5
Synchronous speed (r/min)
6
Line speed (m/min.)
7
Load shaft speed (r/min)
8
Calculated torque value (%)
9
Input power (kW)
10
PID reference value (Final value)
11
PID reference value (remote)
12
PID feedback amount
Set frequency
value (Hz)
Set frequency
value (Hz)
Synchronous speed
set value (r/min)
Line speed set
value (m/min.)
Load shaft speed
set value (r/min)
■
E45 LCD Monitor (Function)
This function selects the item to be displayed on the LCD
monitor in the operation mode.
Set value: 0
Set value: 1
Full-scale value of bar graph
NOTE: The scale cannot be adjusted.
■
E46 Language
This function selects the language for data display on the LCD
monitor.
■
E47 LCD monitor (Contrast)
This function adjusts the LCD contrast. Increase the set value
to raise contrast and decrease to lower contrast.
Value set to E43
Frequency setting
0, 1, 2, 3, 4
Set frequency value (Hz)
5
Synchronous speed set value (r/min)
6
Line speed set value (m/min.)
7
Load shaft speed set value (r/min)
8, 9
Set frequency value (Hz)
10, 11, 12
Set frequency value (Hz)
60.00
60.00
Fout/Iout/TRQ
PRG
→
PRG MENU
F/D
→
LED SHIFT
Hz
A
%
RUN
FWD
60.00
PRG
→
PRG MENU
F/D
→
LED SHIFT
STOP
During running
When stopping
Display item
Full-scale
Output frequency
Maximum frequency
Output current
200% of inverter rated value
Calculated torque value
200% of motor rated value
E47
CONTRAST
E46
LANGUAGE
Set value Language displayed Set value Language displayed
0
Japanese
3
French
1
English
4
Spanish
2
German
5
Italian
E43
LED MNTR
E44
LED MNTR2
For the values 10 to 12 set to E43, the data is displayed only when
selected in “H20 PID control (Mode select).”
•
Display at frequency setting
When a set frequency is checked or changed by the KEY-
PAD panel, the set value shown below is displayed.
Select the display item by using “E43 LED Monitor (Func-
tion).” This display is not affected by “E44 LED Monitor
(Display at STOP mode).”
NOTE:
For the values 10 to 12 set to E43, the data is displayed only when
selected in “H20 PID control (Mode select).”
E45
LCD MNTR
Set value
Display item
0
Operation status, rotating direction, operation guide
1
Output frequency (before slip compensation), output
current, calculated torque value in bar graph
Set value
0, 1, 2 ....................... 8, 9, 10
Screen
Soft
←
→
Hard
Chapter02J(P6˜25).p65
07.8.9, 12:26
Page 25
Adobe PageMaker 6.5J/PPC
Summary of Contents for FRENIC5000G11S Series
Page 1: ......
Page 2: ......
Page 154: ...3 30 3 12 13 P23 30 65p 07 8 9 12 34 Page 30 Adobe PageMaker 6 5J PPC...
Page 166: ...4 12...
Page 182: ...3 12 13 P23 30 65p 07 8 9 12 34 Page 30 Adobe PageMaker 6 5J PPC 5 16...
Page 212: ...3 12 13 P23 30 65p 07 8 9 12 34 Page 30 Adobe PageMaker 6 5J PPC 6 30...
Page 234: ...MEMO Chapter8 4 P15 p65 07 8 9 12 57 Page 18 Adobe PageMaker 6 5J PPC...
Page 235: ......
Page 236: ......