2-71
Chapter 2
4. Standard RS-485 Interface
2
Setting data length
Setting parity bits
Setting stop bits
In a system where the local station is always surely accessed
within a specific time, this function detects that access was
stopped due to an open-circuit or other fault and invoke an Er8
trip.
Setting range: 0: No detection
1 to 60s
Setting transmission speed
Setting action when occurring error and value of timer for the
action
4.8.2 Time of receiving preparation completion
This defines the time from returning the response to complet-
ing receiving preparation of the input port in the inverter.
t
2
: Time of receiving preparation completion
≤
0.1 ms
4.9 Function
■
H30 Serial link (Function select)
The link function (communication function) can connect RS-
485 (provided as standard) to various bus connections
(option).
The link function includes:
1) Monitoring (various data monitoring and function data
check)
2) Frequency setting
3) Operation commands
(Commands such as FWD and REV set at the digital
inputs)
4) Writing function data
Setting link function when communication is valid
Monitoring function and writing function data function are
always valid. If making the communication of digital input
invalid, the state becomes similar to 0 of the setting value.
When option related to busses is provided, this setting in the
function becomes the function selecting of the option, and the
function of RS-485 is restricted only to monitoring and writing
function data. When not providing option, this setting becomes
function selecting of RS-485.
■
H31 RS-485 (Address)
to
■
H39 RS-485 (Response interval)
These set various conditions of the communication through
RS-485. Set these so as to match with upstream devices. For
the protocols, refer to the technical manual.
Setting the station address of RS-485
- Setting range: 1 - 31
H30
LINK FUNC
H31
485ADDRESS
H32
MODE ON ER
H33
TIMER
H34
BAUD RATE
Setting value Frequency setting
Operation command
0
Invalid
Invalid
1
Valid
Invalid
2
Invalid
Valid
3
Valid
Valid
Setting value
Processing at communication error
0
Immediate Er8 alarm (forced stop)
1
Continue operation within timer time,after timer time,
Er8 alarm
2
Continue operation within timer time, and retry
operation. After timer time, Er8 alarm if communica-
tion error, or continue operation if no error.
3
Continue operation
Setting value
Transmission speed
0
19200 bits/s
1
9600 bits/s
2
4800 bits/s
3
2400 bits/s
4
1200 bits/s
H36
PARITY
H38
NO RES t
H37
STOP BITS
H35
LENGTH
Setting value
Stop bit
0
2 bits
1
1 bit
Setting value
Data length
0
8 bits
1
7 bits
Setting value
Parity bit
0
None
1
Even number
2
Odd number
Chapter02J(P44˜74).p65
07.8.9, 12:27
Page 71
Adobe PageMaker 6.5J/PPC
Summary of Contents for FRENIC5000G11S Series
Page 1: ......
Page 2: ......
Page 154: ...3 30 3 12 13 P23 30 65p 07 8 9 12 34 Page 30 Adobe PageMaker 6 5J PPC...
Page 166: ...4 12...
Page 182: ...3 12 13 P23 30 65p 07 8 9 12 34 Page 30 Adobe PageMaker 6 5J PPC 5 16...
Page 212: ...3 12 13 P23 30 65p 07 8 9 12 34 Page 30 Adobe PageMaker 6 5J PPC 6 30...
Page 234: ...MEMO Chapter8 4 P15 p65 07 8 9 12 57 Page 18 Adobe PageMaker 6 5J PPC...
Page 235: ......
Page 236: ......