Chapter 6
2. FRENIC5000G11S/P11S Series
6-5
6
■
Function setting value (Recommended: G11S)
Other than the above functions, some of the basic functions such as base frequency, maximum frequency, acceleration/deceleration time, and
motor characteristics parameters should be set.
■
Tips
1. G11S series for the aeration tank blower
• Because the load characteristics of the aeration tank blower
(route blower) are nearly the constant torque load character-
istics, apply FRENIC5000G11S series.
2. PID control setting values
• The optimum setting values depend on the system due to
various combinations such as the blower characteristics and
water depth of the aeration tank. Therefore, use empirical
values in advance and then reset the values to the optimum
values during test operation.
3. Energy saving operation selection considering
operation condition
• Great energy saving effect can be realized if the system has
enough treatment capacity. Set the energy saving operation
(H10) active, and continue operation unless trouble occurs.
4. Precautions on radio interference
• As many measurement circuits are installed around the
aeration tank, precautions need to be taken for radio noise
interference.
• FRENIC5000G11S series incorporates measures against
radio interference noise generation and a function for
switching to a low carrier frequency. However, we recom-
mend that you take the following action:
1) Install an isolation transformer for the power supply for the
instruments.
2) Use shielded wires for the control signals.
3) Connect Power filter (FHF- / / ) on the inverter power
supply side.
4) Install a ferrite ring for reducing radio noise (ACL-40B or
ACL-74B) on the inverter power supply side.
5) Perform complete wiring separation or electromagnetic
shielding (use metal conduits) for the wiring on the inverter
output side.
5. Full preparation to suppress harmonics with a DC
REACTOR
• An exclusive terminal (P1, P(+)) for connecting a DC
REACTOR is equipped as standard. Connect the optional
DC REACTOR (DCR - ) to reduce harmonics on
power supply side.
6. Suppression of inrush current when the power
supply is turned on
• FRENIC5000G11S series inverters have a built-in circuit that
suppresses inrush current that are generated when the
power supply is turned on. No measures have to be taken to
handle inrush current in particular.
Function
Name
Factory setting
Recommended setting value
Remarks
code
H20
PID control
(Mode select)
H21
(Feedback signal)
H22
(P-gain)
H23
(I-gain)
H24
(D-gain)
H25
(Feedback filter)
E01
X1 terminal
(Function select)
F09
Torque boost 1
H10
Energy-saving operation
H06
Fan stop operation
E20
Y1 terminal
(Function select)
F14
Restart mode after
momentary power failure
(Mode select)
F26
Motor sound
(Carrier freq.)
E24
Y5A,Y5C terminal
function
(Relay output)
F41
Torque limiter 1 (Braking)
C01 to C03
Jump frequency 1 to 3
C04
(Hysteresis)
0: Inactive
1:
Terminal C1 (4 to 20mA) input
0.01: 0.01 times
0.0: Inactive
0.00: Inactive
0.0: No filter
0: Multistep freq. selection
0.0: For constant torque load
0: Inactive
0: Inverter running
1: Inactive
2: 2kHz
15:
Auxiliary terminal for 52-1 [AX]
999: No limit
0: No jump frequency
3: 3Hz
0: Inactive
1: Active
1: Terminal C1 (4 to 20mA) input
0.01 times (= 1%) to 10 times (= 1000%)
0.1 to 3600s
0.1 to 10.00s
0.0: No filter
20: PID control cancel
0.0: For constant torque load
1: Active
1: Active
25: Fan control signal
3: Active
(Continuous operation; heavy inertia
load, or general load)
15: 15kHz
10: 10kHz
0: Inverter running (RUN)
0: Automatic deceleration control
0 to 400Hz
0 to 30Hz
Operation without PID function is
selected.
Set the functions according to
individual system.
Manual operation when input signal is ON.
(Frequency setting with Keypad panel)
Used to control the inverter panel
cooling fans for inverters of 40HP
or larger. Also available with
Functions E1 to E23 (Y2 to Y4
terminal functions).
Set H13 to H16 also, if necessary.
For 75HP or smaller inverter.
For 100HP or larger inverter.
Relay output (Y5A, Y5C). On
when inverter output is present.
(Set if necessary.)
Setting recommended when
braking resistor is not used.
Set the value in accordance with
the equipment to be combined.
Chapter6-2(P4˜5).p65
07.8.9, 12:51
Page 5
Adobe PageMaker 6.5J/PPC
Summary of Contents for FRENIC5000G11S Series
Page 1: ......
Page 2: ......
Page 154: ...3 30 3 12 13 P23 30 65p 07 8 9 12 34 Page 30 Adobe PageMaker 6 5J PPC...
Page 166: ...4 12...
Page 182: ...3 12 13 P23 30 65p 07 8 9 12 34 Page 30 Adobe PageMaker 6 5J PPC 5 16...
Page 212: ...3 12 13 P23 30 65p 07 8 9 12 34 Page 30 Adobe PageMaker 6 5J PPC 6 30...
Page 234: ...MEMO Chapter8 4 P15 p65 07 8 9 12 57 Page 18 Adobe PageMaker 6 5J PPC...
Page 235: ......
Page 236: ......