6-9
6
Chapter 6
2. FRENIC5000G11S/P11S Series
■
Function setting value (Recommended: G11S)
Other than the above functions, some of the basic functions such as base frequency, maximum frequency, acceleration/deceleration time, and
motor characteristics parameters should be set.
■
Tips
1. Setting the base frequency to 50Hz
• Setting the base frequency to 50Hz gets the maximum
performance out of the standard motor, thereby allowing you
to reduce the required acceleration time.
2. Preparing external braking resistor
•
For G11 inverter of 10HP or smaller, a braking resistor is built into
the inverter. However, depending on conditions such as the level of
frequent operation or the load amount, an external resistor (DB -
) having a greater capacity may have to be connected. For 15HP
or larger inverter, a braking unit (BU - ) is required also.
• When the braking resistor is connected externally, be sure to
disconnect the jumper wire (P(+), DB) of the built-in braking
resistor which has been connected at shipping. In addition,
be sure to insulate the disconnected portion.
3. Measures for reducing radio noise
•
At locations where radio waves are weak, radio noise can occur due
to the effect of the wiring on the load side. We recommend that you
install a ferrite ring for reducing radio noise (ACL-40B or ACL-75B)
to reduce radio noise, use metal conduits for wiring, and ground the
control panel, motor, and conduits using lower resistance values.
4.
Full preparation to suppress harmonics with a DC REACTOR
• An exclusive terminal (P1, P(+)) for connecting a DC
REACTOR is equipped as standard. Connect the optional
DC REACTOR (DCR - ) to reduce harmonics on
power supply side.
5. Suppression of inrush current when the power
supply is turned on
• FRENIC5000G11S series inverters have a built-in circuit that
suppresses inrush current that are generated when the
power supply is turned on.
6. Keypad panel designed with six foreign lan-
guages as standard
1) Standard products : English, German, French, Spanish,
Italian, and Japanese
2) Manufactured on request : Chinese, English, and Japanese
Function
Name
Factory setting
Recommended setting value
Remarks
code
F10
Electronic thermal relay for motor 1
F11
(Select)
F12
(Level)
(Thermal time constant)
F42
Torque vector control 1
P01
Motor 1
(No. of poles)
P02
(Capacity)
P03
(Rated current)
P04
(Tuning)
P05
(On-line tuning)
P06
(No-load current)
P07
(%R1 setting)
P08
(%X setting)
P09
(Slip compensation control)
A06
Electronic thermal relay for motor 2 (Select)
A07
(Level)
A08
(Thermal time constant)
A09
Torque vector control 2
A10
Motor 2
(No. of poles)
A11
(Capacity)
A12
(Rated current)
A13
(Tuning)
A14
(On-line tuning)
A15
(No-load current)
A16
(%R1 setting)
A17
(%X setting)
A18
(Slip compensation control)
E07
X7 terminal (Function select)
H06
Fan stop operation
F26
Motor sound
(Carrier freq.)
F14
Restart mode after momentary
power failure
(Mode select)
1: Active (Standard motor)
100% of motor rated current
5.0min (30HP or smaller)
10.0min (40HP or larger)
0: Inactive
4: 4-pole
Capacity of motor used
Fuji’s standard value
0: Inactive
0: Inactive
Fuji’s standard value
Fuji’s standard value
Fuji’s standard value
Fuji’s standard value
1: Active (Standard motor)
100% of motor rated current
5.0min (30HP or smaller)
10.0min (40HP or larger)
0: Inactive
4: 4-pole
Capacity of motor used
Fuji’s standard value
0: Inactive
0: Inactive
Fuji’s standard value
Fuji’s standard value
Fuji’s standard value
Fuji’s standard value
6:
3-wire operation stop command
0: Inactive
2: 2kHz
1: Inactive
1: Active (Standard motor)
100% rated current of motor used
5.0min (30HP or smaller)
10.0min (40HP or larger)
1: Active
2 to 14: 2- to 14-pole
1/8 to 60HP: 30HP or smaller
1/8 to 800HP: 40HP or larger
0.00 to 2000A
1: Active
1: Active
0.00 to 2000A
0.00 to 50.00%
0.00 to 50.00%
0.00 to 5.00Hz
1: Active (Standard motor)
100% rated current of motor used
5.0min (30HP or smaller)
10.0min (40HP or larger)
1: Active
2 to 14: 2- to 14-pole
1/8 to 60HP: 30HP or smaller
1/8 to 800HP: 40HP or larger
0.00 to 2000A
1: Active
1: Active
0.00 to 2000A
0.00 to 50.00%
0.00 to 50.00%
0.00 to 5.00Hz
12: motor2/motor1
1: Active
15: 15kHz
10: 10kHz
0: Inactive
(Trip and alarm when power failure occurs.)
Set if necessary.
Set according to the motor used.
Set according to be motor used before tuning.
Set P04 first, and then P05.
Values are detected and written
automatically during tuning.
Set the value in accordance with
the equipment to be combined .
Set if necessary.
Set according to the motor used.
Set according to be motor used before tuning.
Set A13 first, and then A14.
Values are detected and written
automatically during tuning.
Set the value in accordance with
the equipment to be combined.
For 75HPor smaller inverter.
For 100HP or larger inverter.
Set H13 to H16 also, if necessary.
Chapter6-4(P8˜9).p65
07.8.9, 12:51
Page 9
Adobe PageMaker 6.5J/PPC
Summary of Contents for FRENIC5000G11S Series
Page 1: ......
Page 2: ......
Page 154: ...3 30 3 12 13 P23 30 65p 07 8 9 12 34 Page 30 Adobe PageMaker 6 5J PPC...
Page 166: ...4 12...
Page 182: ...3 12 13 P23 30 65p 07 8 9 12 34 Page 30 Adobe PageMaker 6 5J PPC 5 16...
Page 212: ...3 12 13 P23 30 65p 07 8 9 12 34 Page 30 Adobe PageMaker 6 5J PPC 6 30...
Page 234: ...MEMO Chapter8 4 P15 p65 07 8 9 12 57 Page 18 Adobe PageMaker 6 5J PPC...
Page 235: ......
Page 236: ......