2-61
Chapter 2
4. Standard RS-485 Interface
2
4.5 Functions specific for communication
To operate the inverters or to monitor the state via communi-
cation, the following functions are specifically available for
communication in addition to the functions for parameter
change of the inverters. These functions adopted the common
data format applicable to the types on and after G11/P11
series, so that it is possible to access to the different type by
the same program on the host side.
4.5.1 Command data
Note:
1) If both S01 and S05 are set (Data writing except 0), command of
S01 becomes valid.
2) The data writing exceeding the setting range is possible, but the
actual action will be restricted within the inverter.
3) When the command data shown here are read, it is not the
command data of actual action but the command data communi-
cated before (the final command data can be obtained by reading
of the monitoring data described later).
4.5.2 Operation command data
S01
Setting frequency (p.u.)
-
-20000 to +20000
1
R/W
(Maximum frequency at
±
20000)
S05
Setting frequency
Hz
0.00 to 400.00 (P11S: 0.00 to 120.00)
0.01
R/W
Code Name
Unit Variable range
Min. unit
Read/write
S06
Operation command
-
Refer to the data format [14]
-
R/W
S07
Universal Do
-
Refer to the data format [15]
-
R/W
S12
Universal Ao
-
-20000 to +20000 (100% output at
±
20000) 1
R/W
Code Name
Unit Variable range
Min. unit
Read/write
Warning
Be sure to check no run command because of sudden start when the alarm is reset while a run
command through RS-485 is remained.
There is a fear of failure.
Note:
1) Since X1-X9 are multi-function inputs, it is necessary to set the
functions with E01-E09.
2) The alarm reset is executed, when RST signal changes from ON to
OFF even there are no alarming factors.
3) Universal Do is a function utilizing inverter's Do via transmission.
(In detail, refer to the detail descriptions E20-E24 in "Function
Explanation" in the instruction manual of inverter).
4) The data writing exceeding the setting range is possible, but the
actual action will be restricted within the inverter.
5) When the operation command is instructed through the communi-
cation, the relation to the inverter terminal commands becomes as
follows.
Chapter02J(P44˜74).p65
07.8.9, 12:26
Page 61
Adobe PageMaker 6.5J/PPC
Summary of Contents for FRENIC5000G11S Series
Page 1: ......
Page 2: ......
Page 154: ...3 30 3 12 13 P23 30 65p 07 8 9 12 34 Page 30 Adobe PageMaker 6 5J PPC...
Page 166: ...4 12...
Page 182: ...3 12 13 P23 30 65p 07 8 9 12 34 Page 30 Adobe PageMaker 6 5J PPC 5 16...
Page 212: ...3 12 13 P23 30 65p 07 8 9 12 34 Page 30 Adobe PageMaker 6 5J PPC 6 30...
Page 234: ...MEMO Chapter8 4 P15 p65 07 8 9 12 57 Page 18 Adobe PageMaker 6 5J PPC...
Page 235: ......
Page 236: ......